Blog
BEI Malaysia: Scoring Your Building's Cooling by Measuring It
What Malaysia's Building Energy Index and MS1525 reveal about the hidden cooling waste in a building that feels perfectly fine — and why you can't fix a plant you don't…

Part 16 of 20 in Cobler's Cooling Fundamentals course. New here? See the course page.
A poorly run building can feel perfectly fine on a hot afternoon. Upstairs it's cool, quiet and comfortable.
But down in the plant room, the chillers may be using far more electricity than they need. Pumps may be running at full speed for no reason, and a fouled condenser may be adding to every kilowatt-hour.
None of this reaches the people upstairs. It only shows up as an electricity bill that's bigger than it should be.
So how do we see it? We measure it. That means flow, temperature and power, turned into the kW per ton from Part 13.
Then we'll see how to prove a change saved energy, and how the Building Energy Index (BEI) scores the whole building.
Two numbers
To grade a cooling plant, we need two numbers at the same moment:
- The cooling delivered, in kW or RT (1 RT = 3.517 kW of cooling, from Part 5).
- The electricity used by the plant, in kW.
Divide the second by the first, and we get the plant's real kW per ton.
Now, earlier parts used figures like kW per ton, delta-T and part-load efficiency as if we could read them off a dial. But in most buildings we can't, because there's no gauge that shows them. They have to be calculated from three kinds of measurement, which are flow, temperature and power.
Measuring the cooling
The chilled water carries heat from the building back to the chillers. As we saw in Part 9, the cooling it carries is the flow multiplied by how much the water warms up on its trip:
$$Q_{\text{cooling}}\ (\text{kW}) = \text{flow (L/s)} \times 4.19 \times \Delta T\ (^\circ\text{C})$$
To use that on a real plant, we need two kinds of instrument:
- A flow meter on the chilled water pipe, to measure how many litres per second are moving.
- Temperature sensors on the supply and return pipes, to measure delta-T.
Say the office tower's meters read a flow of 126 L/s on a hot afternoon, with supply at 6.0 °C and return at 12.0 °C. Then the cooling delivered is 126 × 4.19 × 6, about 3,170 kW.
Dividing by 3.517 gives about 900 RT, which is the building's peak cooling load.
Those two temperature sensors need to be accurate, and checked against each other. Small errors matter, because on a delta-T of 6 °C, a temperature error of only 0.3 °C is a 5% error in the cooling figure. And that's a 5% error in kW per ton too.
Worth knowing: Part 17 uses these same two sensors to spot a common fault called low delta-T.
Measuring the electricity
The other half of the ratio is the electricity. For that we need power and energy (kWh) meters on the plant's electrical supply. How electricity meters work explains what they record.
But first we have to decide what we're measuring. As Part 13 explained, a chiller-only figure counts only the chillers. A whole-plant figure also counts the chilled water pumps, condenser water pumps and cooling tower fans.
The whole-plant figure is the one the bill follows, so we meter all of them, or meter the plant's switchboard as a whole. That's why the office tower has a sub-meter on its chiller plant.
Suppose the plant meter reads 855 kW at the same moment as those flow and temperature readings. Then:
- kW per ton = 855 ÷ 900, about 0.95 kW/RT
- COP = 3,170 ÷ 855, about 3.7
That matches the office tower's measured figure of 0.95 kW/RT, against its design target of 0.85. And the gap between the two is waste we can now see and put a number on.
But remember from Part 13 to compare a whole-plant measurement only with whole-plant figures, not with a chiller's nameplate.

Three kinds of measurement feed one calculation. Flow and delta-T give the cooling delivered, the power meters give the electricity used, and the ratio is the real kW per ton.
Following the numbers
One set of readings tells us where the plant is at one moment. But it doesn't tell us whether that's normal. Efficiency changes with the load, the weather and the slow fouling of heat exchangers, as Part 15 explained.
So the readings need to be collected all the time, for example every 15 minutes, and stored. Then a monitoring system does the arithmetic for every interval. With that record, we can:
- see a trend, such as kW per ton slowly rising over months as tubes foul,
- compare like with like, such as this month's hot afternoons against last month's, and
- get an alert when something changes suddenly, such as delta-T falling after a valve fault.
It's the same idea as the electricity meter at your incoming supply, applied inside the plant.
Worth knowing: if your building has split units and cassettes, like the shoplot, there's no chilled water pipe to put a flow meter on. So the practical step is to sub-meter the air-conditioning circuits. Then compare their kWh with room temperatures and operating hours over time.
Proving a saving
Once we can measure, we can check whether a change really saved energy. The method is called measurement and verification (M&V):
- Baseline. Before changing anything, record the plant's energy use in kWh over a representative period. Record the things that affect it too, such as outdoor temperature, occupancy and operating hours.
- Make one change. For example, reset the chilled water temperature, fix a low delta-T, enable variable-speed pumping or correct the chiller staging.
- Measure again and compare. Record the energy use after the change, and adjust for any difference in weather and occupancy. Then show the saving in kWh.

The saving is the gap between the baseline, adjusted for weather and occupancy, and what the plant actually used after the change.
The third step is the one most often skipped, because the building feels just as cool before and after, so there's no other feedback.
"We changed the settings and it feels better" isn't evidence. "Plant consumption dropped 14% after adjusting for weather, and stayed there for three months" is.
How a saving becomes ringgit depends on the tariff. On a Medium Voltage tariff like the office tower's, a saving cuts the energy charge. If it lowers the month's highest half-hour, it cuts the demand charge too.
On a Low Voltage tariff like the shoplot's, it comes only through kWh. Part 14 explains these charges.
BEI
Everything so far measures the cooling plant. But there's also a single score for the whole building, the Building Energy Index, or BEI, also called building energy intensity:
$$\text{BEI} = \frac{\text{total annual building energy (kWh)}}{\text{gross floor area (m}^2)}$$
The result is in kWh/m²/year, the kilowatt-hours used per square metre of floor per year. Dividing by floor area lets us compare buildings of different sizes.
A 40,000 m² tower will always use more kWh than a 10,000 m² one, but per square metre, the two can be compared.
The office tower uses about 6,000,000 kWh a year over 30,000 m² of gross floor area, not counting the car park. So its BEI is 6,000,000 ÷ 30,000 = 200 kWh/m²/year.
How does that compare? Here are some rough reference points, which change with building type and with the edition of the guidance you use:
- Typical Malaysian offices are often quoted at about 200 to 250 kWh/m²/year.
- A few national showcase green buildings report about 30 to 90 kWh/m²/year.
Worth knowing: two BEI figures are only comparable if they're calculated the same way. Some schemes remove car-park energy and floor area, or adjust for operating hours. Our BEI guide explains the Malaysian definitions and labelling.
BEI also appears in Malaysia's Green Building Index (GBI) rating, where a lower BEI earns points. It sits alongside MS 1525, the Malaysian Standard code of practice on energy efficiency and use of renewable energy for non-residential buildings.
That standard covers the building envelope, lighting, air conditioning and more. Before you quote a BEI target in a report, check the current edition of the standard or scheme you're citing, because benchmarks get revised.
What BEI can't tell us
In an air-conditioned Malaysian office, cooling typically takes about 40 to 60% of the electricity (Part 14). So cooling has the biggest effect on BEI.
Replacing every light with LEDs saves a few percent. But the large gap between a typical building and a showcase one is mostly in the plant room.
But BEI is an annual total for the whole building. It tells us how much energy the building uses, but not why, or where. A high BEI doesn't show whether the cause is a low delta-T, badly staged chillers or long operating hours.
For that, we need the plant measurements from earlier. So the two work together. BEI is the score, and flow, temperature and power show what's behind it.
Reading a fault
So now we can measure the cooling delivered, the electricity used and the kW per ton, and we can prove a saving. And once we're measuring, faults start to show.
The same two temperature sensors on the supply and return pipes reveal one of the most common. So what does it look like when the chilled water comes back too cold, and why does that waste energy? That's Part 17: Low Delta-T Syndrome.
Check your understanding
1. A chilled water flow meter reads 50 L/s, the supply is 6 °C and the return is 11 °C. The plant meter reads 300 kW. What are the cooling delivered and the kW per ton?
Show the answer
Cooling = 50 × 4.19 × 5, about 1,048 kW, which is 1,048 ÷ 3.517, about 298 RT.
So the kW per ton is 300 ÷ 298, about 1.0 kW/RT. That's in the "average" band for a whole plant.
2. Your building's BEI hasn't changed in two years. Does that mean the cooling plant is performing as well as ever?
Show the answer
Not necessarily. BEI is an annual whole-building total. A plant getting less efficient could be hidden by other changes, such as fewer operating hours or lower occupancy.
Only the plant's own flow, temperature and power measurements show its kW per ton.
Recap
- To grade a cooling plant, we need the cooling delivered and the electricity used at the same moment.
- The cooling comes from a flow meter and supply and return temperature sensors (flow × 4.19 × delta-T). The electricity comes from power meters on the chillers, pumps and tower fans.
- Their ratio is the real kW per ton, and it needs following over time.
- M&V proves a saving: a baseline, one change, then measuring again with adjustments for weather and occupancy.
- BEI (annual kWh ÷ gross floor area) scores the whole building, but only the plant measurements show why the score is what it is.
Go deeper on video (optional)
This video shows how a building's chillers, cooling tower and air handling units work together. It's a useful picture of the plant whose performance we're measuring, and of where the flow, temperature and power meters would go. You won't need it for the next part.
This is Part 16 of 20 in Cobler's Cooling Fundamentals course. Previous: Why Chiller Efficiency Is Measured at Part Load: Understanding IPLV. Next: Low Delta-T Syndrome: The Silent Efficiency-Killer of Chilled-Water Plants.
Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.
FAQ
Frequently asked questions
BEI (Building Energy Index, also called building energy intensity) is a building's total annual energy use divided by its gross floor area, in kWh/m²/year. It gives one whole-building score you can compare with other buildings regardless of size. Typical Malaysian offices are often quoted at about 200 to 250 kWh/m²/year, and a few national showcase green buildings report about 30 to 90. Schemes differ in what they include (for example car parks and operating hours), so check the current edition and method before comparing against a target.
In Malaysia's hot, humid climate, cooling typically takes about 40 to 60% of an air-conditioned office's electricity, so it has the biggest effect on BEI. But BEI only tells you how much energy the whole building uses, not why. To learn what is behind the score, you need to measure the cooling plant itself. That means chilled-water flow, supply and return temperatures, and the electricity used by the chillers, pumps and tower fans.
Three kinds of measurement, feeding a monitoring system. The first is a flow meter on the chilled-water loop. The second is temperature sensors on the supply and return pipes. The third is power/kWh meters on the chillers, pumps and cooling-tower fans. Flow × 4.19 × delta-T gives the cooling delivered in kW. Dividing the plant's electrical kW by the cooling in RT gives the real kW per ton. Without these measurements, efficiency is a guess.
Ask us about this topic
Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.


