Blog
Water Tank Level Control in Buildings
Float valves, level switches and electrode probes decide when your tanks fill and when your pumps run. When one sticks, the water leaves quietly through the overflow pipe and nobody notices for weeks.

Part 3 of 12 in Cobler's Water Fundamentals course. New here? See the course page.
Nobody stands on the office tower's roof watching the tanks. Yet all day the roof tanks empty as people use water, and they fill up again before the top floors run short.
Down at ground level, the suction tank does the same with water from the street. So who's doing that job?
Well, it's done by a few small devices: float valves, electrode probes, float switches and level sensors. Together they do what we call water tank level control.
When they work, nobody thinks about them. But when one fails, water can run out of an overflow pipe into a drain for weeks before anyone notices.

The office tower has two tanks to control: the suction tank at ground level and the roof tanks.
Water tank level control
Let's start with what a tank needs. Every tank needs two kinds of control:
- Inlet control lets water in when the level drops, and stops it when the tank is full.
- Pump control starts and stops the pumps that fill or empty the tank, and protects them.
Here's how the office tower does it, and we'll use this arrangement for the rest of the course.
- The suction tank is filled from the bulk meter by the main's own pressure. A float valve on its inlet lets water in and shuts when the tank is full, with no electricity involved.
- The roof tanks are filled by the transfer pumps. Electrode probes in the roof tank tell the pump panel when to start a pump, because the level has dropped to the start point. They also say when to stop it, because the level has reached the stop point. The inlet has a float valve too, as a backup, and we'll see why at the overflow.
- A low-level probe in the suction tank stops the transfer pumps if the suction tank runs low, so they never pump air. A pump that runs dry for a few minutes can destroy its seal.
This matches the plumbing guidelines of SPAN (Suruhanjaya Perkhidmatan Air Negara, the National Water Services Commission). They say the pumps should run automatically, using stainless steel electrodes in both the suction tank and the roof tank. They also ask for an alarm when the roof tank level falls below the pump start level.
The shoplot is simpler. The main's pressure reaches its roof tank directly, so its roof tank has a float valve on the inlet and no pumps at all.
Float valves
So the inlet control comes down to the float valve, and it's a lovely bit of plain mechanics. It's a valve on the tank inlet with a float on an arm.
As the water rises, the float rises with it, and the arm pushes a washer against a seat inside the valve until the flow stops. It needs no power, no wiring and no programming. You'll also hear it called a ball valve or a ballcock.
The 2014 plumbing rules set three requirements for the inlet of a storage tank:
- It must have a float valve, or another good way to control the inflow and prevent overflow. That valve must shut tight against twice its normal working pressure.
- The valve's outlet must be at least 75 mm above the water line. We call this gap an air gap. Because the outlet never touches the water, tank water can't be sucked back into the supply if the main loses pressure. Part 5 explains air gaps and backflow in full.
- The inlet must discharge at least 25 mm above the tank's overflow level.
Large tanks often use a delayed-action or equilibrium float valve. You'd expect a float valve to close slowly as the level rises, and an ordinary one does.
But this kind stays fully shut until the level has dropped by a set amount, then opens fully. That avoids the constant half-open dribble that wears out seats.
Float valves fail in three common ways:
- The washer hardens or gets damaged by grit, so the valve no longer seals. Water keeps weeping through even when it's "shut".
- The arm bends or the pivot corrodes, so the valve closes late or not at all.
- The float gets a pinhole. It slowly fills with water, sinks, and holds the valve open.
In each case the tank keeps taking water after it's full, and the extra water leaves through the overflow pipe.
The cost of a stuck float valve
So how much can a small fault like that waste? More than you'd guess.
Take an illustrative case. A 25 mm float valve fails partly open and passes about 0.3 litres per second into a tank that's already full. That's about 26 cubic metres a day going straight down the overflow, or about 780 cubic metres a month.
Now say it happened on the office tower's suction tank. All of that water would pass through the bulk meter, so all of it would be billed, for water and partly for sewerage too. And 780 m³ is about a quarter of the tower's normal month.
Part 7 puts a ringgit price on each extra cubic metre, and a float valve washer costs very little by comparison.
Probes, switches and sensors
The float valve handles the inlet on its own. But the pumps are a different story, because an electrical panel controls them, and the panel needs to know the water level. So something has to turn the level into a signal, and three kinds of device do that.
Electrode probes are metal rods hung from the tank lid at different depths, and you'll also hear them called conductivity probes. Water conducts a small current, so when the water touches a rod, it completes a circuit between that rod and a longer common rod.
One rod marks the pump start level, one the pump stop level and one the high-level alarm. They have no moving parts.
Their weakness in warm tanks is fouling, where scale and slime coat the rod tips and the panel stops seeing the water properly. So clean them whenever the tank is cleaned.
Float switches are sealed plastic floats hanging on a cable. As the water passes them, they tilt and open or close a contact. They're cheap and easy to replace.
They fail when the cable wears out where it enters the float, or when the float snags on a pipe or ladder. They also fail when someone rehangs one at the wrong depth after cleaning.
Continuous level sensors measure the real level, in metres or per cent, instead of a few on and off points. We also call them level transmitters. One type is an ultrasonic sensor looking down from the lid, and another is a pressure sensor at the bottom of the tank.
A continuous level lets us see how fast the tank fills and empties, and later parts use that to measure the building's water use. The office tower has a level transmitter on the suction tank and on the roof tanks, alongside the probes.

The suction tank's float valve controls its inlet. Probes in the roof tank start and stop the transfer pumps, and a probe in the suction tank stops them if it runs low.
Layers of protection
So what happens when one of these devices fails? Good practice is to protect a tank with several layers, where each one catches the failure of the one before. Here's our roof tank, from the lowest layer to the highest:
- The pump stop probe is the main control. It stops the transfer pump when the tank is full.
- The high-level alarm probe, a little higher, raises an alarm if the level goes past the stop point.
- The backup float valve on the inlet shuts if the level keeps rising.
- The overflow pipe, higher still, lets water out safely, so the tank doesn't burst or flood the roof.
Try it
The suction tank has fewer layers. Its float valve is the main control, and the overflow is right behind it. And if your only protection against overflow is one float valve, a single worn washer is enough to waste water.
Now here's an idea that later parts lean on. An overflowing tank is at its highest level.
Say the roof tank is overflowing and the transfer pump is still running. Then the stop probe or its panel has failed, and so has the backup float valve. The pump isn't "trying to fill" the tank. Part 4 uses this to diagnose pumps.
The overflow is a safety device, and it's not meant to carry water in normal use. So any flow through it means something has failed.
SPAN's guideline says tanks larger than 4,500 litres should have a separate warning pipe as well as the overflow. A warning pipe is a small pipe set just above the normal water line, with its outlet somewhere obvious. Both should discharge somewhere people can see them.
Smaller tanks can use one overflow pipe as the warning pipe, as long as it discharges where people can see it.
Two practical steps make an overflow hard to miss:
- Make the discharge visible. Run it to a place people walk past, not into a hidden floor drain on the roof.
- Put a small flow switch or meter on the overflow and wire it to an alarm, so any flow sends a message. If the tank has a continuous level sensor, a high-level alarm does the same job without changing the pipework.
A passing float valve on the suction tank also shows up on the bulk meter. If the suction tank is full and the meter is still turning in the middle of the night, water is leaving somewhere. It's going out through the overflow, or through a leak.
Worth knowing: be careful the other way round, too. A bulk meter turning at 3am may only be the suction tank refilling after the day's use. Part 10 explains how to tell the two apart.
How much storage a building needs
So how big should these tanks be? Sizing balances two needs. With too little storage, a supply interruption empties the building by lunchtime.
With too much, water sits in the tanks for a long time. In warm tanks the chlorine left in the water to disinfect it fades over time, and stale water becomes a hygiene risk.
The sizing rules for domestic water storage come from SPAN's Uniform Technical Guidelines and the water operator. They don't come from the Uniform Building By-Laws, which mainly deal with fire.
SPAN's guideline says storage should provide one day's water use, and it gives minimum figures for different buildings. Two of them match our example buildings:
- Offices and commercial buildings (domestic use): 1,000 litres per 100 square metres of floor area. The office tower has 30,000 square metres, so its minimum is 300,000 litres, or 300 m³.
- Three-storey shop house: 4,100 litres. That's the minimum for a building like the shoplot.
The guideline also says the suction tank should hold 30 to 70 per cent of the daily storage, and the roof tanks the rest. The office tower's two roof tanks hold 100 m³ each, so its 300 m³ suction tank is 60 per cent of the 500 m³ total.
Hospitals, airports and medium and heavy industries need at least two days' storage. And fire water is always stored separately, because daily needs must never use it up.
These are minimum design figures, and the water a building really uses is often lower. Our tower's 1,500 people use about 75 m³ of domestic water on a working day, which is about 50 litres each.
The cooling towers add about 60 m³, so a normal working day is about 100 to 140 m³. So the 300 m³ suction tank holds about two to three days of normal use. A year of meter readings tells you your own real use.
Part 5: Keeping Stored Water Safe explains why water that stays too long in a tank is a problem.
Checking the controls
The best time to check the level controls is when the tank is drained for cleaning, because everything inside is within reach.
SPAN's guideline says owners of premises such as offices and shops should inspect, clean and disinfect their tanks at regular intervals, on a voluntary basis. It doesn't set a fixed interval for them, and Part 5 covers tank cleaning, water quality and who's responsible.
So use each visit to check the controls:
- Check the float valve seat and washer, and replace worn parts before they fail.
- Check that the float hasn't taken on water, and that the arm and pivot move freely.
- Clean the electrode probe tips, and check that each one still switches at the right level.
- Test the high-level alarm and any inlet valve by raising the level or lifting the float. Don't assume they work.
- Check that the overflow and warning pipe are clear, screened against insects, and discharging where someone would notice.
- Check that the lid seals, the vents are screened and no light reaches the water.
Write the switching levels on the tank or in the pump panel, and it's best to do it before the cleaners start. The most common fault after a cleaning visit is a float switch or probe rehung at the wrong height.
Too small a gap between start and stop makes the transfer pump start every few minutes. A stop point set too high leaves the roof tank much fuller than intended, or lets it reach the overflow.
Optional detail: where the rules in this part come from.
- The inlet requirements are in Rule 47 of the Water Services Industry (Water Reticulation and Plumbing) Rules 2014. They cover the float valve that shuts tight against twice its working pressure, the 75 mm air gap and the 25 mm overflow gap.
- The rest of this part draws on SPAN's Uniform Technical Guidelines for Water Reticulation and Plumbing (April 2018). Section C.3.3 has storage of one day's use, the minimum figures per building type and the warning pipe for tanks over 4,500 litres.
- In the same guidelines, the air gap is in C.4.1, and the electrodes and the 30 to 70 per cent share are in C.3.5. Voluntary cleaning is in C.4.2.
The pumps at the other end
So now we know how each tank decides when it's full and when it's low. The float valve looks after the suction tank's inlet by itself, and the probes hand the roof tanks over to the transfer pumps. But so far we've treated those pumps as a black box.
So what does a pump do to the water, and what is it telling us when it starts too often, or never stops at all? That's Part 4: Water Pumps in Buildings Explained.
Check your understanding
1. At 3am the roof tank's overflow pipe is running and the transfer pump is still on. What has failed?
Show the answer
An overflowing tank is at its highest level, so a working stop probe would already have stopped the pump. So the stop probe or the pump panel has failed, for example a fouled or disconnected probe, or a panel left in manual.
And the backup float valve on the roof tank inlet isn't shutting either.
2. The roof tank's stop probe already stops the transfer pump when the tank is full. Why does the inlet also have a float valve?
Show the answer
It's a backup layer. If the stop probe fouls or its panel fails, the pump keeps running and the level keeps rising. The backup float valve then shuts the inlet before the water reaches the overflow.
The high-level alarm, between the two, warns that the first layer has failed.
Recap
- Every tank needs inlet control and pump control.
- In the office tower, a float valve controls the suction tank inlet, and electrode probes in the roof tank start and stop the transfer pumps. A low-level probe in the suction tank stops the pumps running dry.
- The 2014 plumbing rules ask for a float valve or equivalent and a 75 mm air gap on tank inlets.
- Float valves fail by leaking, sticking or sinking, and a small leak can waste hundreds of cubic metres a month.
- An overflowing tank is at its highest level, so any overflow means a control has failed. Overflows should be visible and alarmed.
- SPAN's guideline sizes storage for one day's use, which for our tower means at least 300 m³.
This is Part 3 of 12 in Cobler's Water Fundamentals course. Previous: Water Pressure in Buildings, Explained. Next: Water Pumps in Buildings Explained.
Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.
FAQ
Frequently asked questions
Look at the tank and its overflow. If the tank is full and water is running from the overflow or warning pipe, the inlet valve is not shutting. On a suction tank fed from the mains, there is a second sign. The bulk meter is still turning in the middle of the night while the tank is already full. Be careful, because a meter turning at night can also be the tank refilling normally after the day's use. So check the tank level at the same time. A continuous level sensor, or a flow switch on the overflow wired to an alarm, makes this visible without a site visit.
A float switch is a sealed float on a cable that tilts as the water passes it and opens or closes an electrical contact. An electrode probe has no moving parts. It uses the water itself to complete a small circuit between a common rod and rods cut to different lengths. Each rod marks one switching point, such as pump start, pump stop or the high-level alarm. Float switches fail from cable wear, snagging or being rehung at the wrong depth. Probes fail when scale and slime coat their tips, which is common in warm Malaysian tanks. SPAN's Uniform Technical Guidelines call for stainless steel electrodes in both the suction tank and the roof tank to run the pumps.
For offices, shops and similar premises, SPAN's Uniform Technical Guidelines (section C.4.2) cover this. They say owners should inspect, clean and disinfect their tanks at regular intervals, on a voluntary basis, and they do not set a fixed interval. For shared tanks in high-rise residential buildings and gated communities, the guideline refers to separate maintenance rules. Check your water operator's and local authority's current guidance, and set an interval based on the tank's condition and inspection results. Use every cleaning visit to also inspect the float valve, level switches, probes and overflow. Part 5 of the course covers stored water safety in more detail.
Yes. An overflow pipe is a safety device, so any flow through it means a control has already failed. SPAN's guideline asks tanks larger than 4,500 litres to have a separate warning pipe and overflow, both discharging at a visible place. A small flow switch or meter on the overflow line, wired to an alarm, turns a silent fault into a notification. If the tank already has a continuous level sensor, a high-level alarm gives the same warning without changing the overflow pipework.
SPAN's Uniform Technical Guidelines size domestic storage for one day's use and give minimum figures by building type. For offices and commercial buildings, it is 1,000 litres per 100 square metres of floor area. For a three-storey shop house, it is 4,100 litres. The suction tank should hold 30 to 70 per cent of the total, with the rest in the roof tanks. Fire storage is kept separate. Hospitals, airports and medium and heavy industries need at least two days. Confirm the requirement with SPAN's guideline and your water operator. Oversized storage has a cost, because water that stays too long in a warm tank loses its chlorine and becomes a hygiene risk.
Ask us about this topic
Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.


