Water FundamentalsPart 4 of 12

Blog

Water Pumps in Buildings Explained

Transfer pumps, booster sets, duty/standby arrangements and float interlocks, explained without the hydraulics jargon. Learn what short-cycling and a pump that never stops are trying to tell you, and why every leaking cubic metre costs you twice.

Tan Kok XinTan Kok XinWater Fundamentals
Water Pumps in Buildings Explained - illustration

Part 4 of 12 in Cobler's Water Fundamentals course. New here? See the course page.

The probes in the office tower's roof tanks only ever send one message to the pump panel, start or stop. At the other end of that wire is a pump.

In fact the tower has two sets. The transfer pumps lift water from the suction tank to the roof tanks. The booster set raises the pressure on levels 19 and 20 (Part 2).

Water pumps in buildings are some of the few machines that work around the clock. But they're rarely metered on their own, so their electricity cost hides inside the building's total bill.

They're also a handy diagnostic tool, because their pattern of starts shows things a monthly bill can't. So let's see what a pump does, and then learn to read what it's telling us.

The example office tower schematic with the pumps highlighted: the duty and standby transfer pumps next to the suction tank at ground level, and the booster set on the roof serving levels 19 and 20

The office tower has two sets of pumps: transfer pumps at ground level and a booster set on the roof.

Try it

Loading the interactive

What a pump adds

So what does a pump do to the water? It doesn't make any, of course. It adds pressure, and in water terms that's the same as adding height, or head.

Part 2 gave us the rule, about 10 metres of head for every 1 bar. So a pump that adds 3 bar can push water about 30 metres up, if nothing else gets in the way.

But something always gets in the way. Every pump has to provide two things:

  1. Static lift is the height from the water surface the pump draws from to the point it delivers to. For our tower's transfer pumps, from the suction tank up to the roof tanks, that's about 80 metres.
  2. Friction loss is the extra pressure lost as water rubs along pipe walls and passes valves and bends. Part 2 showed that it grows quickly with flow.

Long horizontal runs and undersized pipes add to the friction. That's why two buildings of the same height can need quite different pumps.

Transfer pumps and booster sets

So what are the tower's two sets of pumps doing with that pressure? People often mix them up, but they do different jobs and fail in different ways.

A transfer pump moves water from one tank to another. In our tower, it draws from the suction tank and pushes water up the rising main into the roof tanks.

It doesn't care about the pressure at any tap, and only responds to the roof tank level. When the level falls to the start probe, the pump runs at more or less full flow. It stops when the level reaches the stop probe (Part 3).

SPAN's plumbing guidelines ask that the duty pump can fill the roof tank of an office or commercial building within eight hours. So transfer pumps have long runs and few starts.

A booster set holds a pressure instead of filling a tank. In our tower it draws from the roof tank and serves levels 19 and 20. Those floors are too close to the tank for gravity to give enough pressure (Part 2). Taller buildings with several pressure zones may have a booster set for each zone.

A booster set is a package of two or more pumps, controlled by a pressure switch or pressure sensor on its outlet pipe. Most also have a pressure vessel. That's a small tank with a rubber bag, or bladder, inside it and a cushion of compressed air.

The vessel stores a little water under pressure. So a small draw, such as one tap for a few seconds, doesn't need a pump to start.

SPAN's guideline calls for either a duty and standby set of this kind, which we call hydro-pneumatic, or a variable speed set.

A variable speed drive (VSD) is an electronic unit that changes the speed of the pump motor. With a VSD, the pump speeds up and slows down to hold a steady pressure, instead of switching fully on and off. And running a pump slower than full speed uses much less power.

How Electric Motors Work, in the Electricity Fundamentals course, explains motors and speed control.

Duty and standby

Now, walk into almost any pump room and you'll see the pumps come in pairs or threes. Why? The usual arrangement is duty and standby, where one pump does the work while the other waits.

Larger systems use duty, assist and standby, where a second pump cuts in when one can't keep up, and a third waits in reserve. SPAN's guideline also asks for a backup generator on pumping systems in buildings other than landed houses, so water keeps moving in a power cut.

A good control panel swaps the duty pump on every start, or on a timer, so the pumps share the running hours. That matters more than it sounds.

A pump that hasn't run for six months often has stiff seals and a corroded shaft. And it may fail on the very day the duty pump breaks down. So if the standby pump shows zero hours in the log, the building doesn't really have a standby, and swapping the duty pump costs nothing.

It's also worth checking that both pumps can still do the job. Impellers, the spinning parts that move the water, wear down, and non-return valves stick. A set designed for one pump to do the work can slowly decline until it needs both.

What tells a pump to run

So each kind of pump takes its orders from a different signal:

  • Transfer pumps follow the roof tank level. In the office tower, the start and stop probes in the roof tanks switch them. The low-level probe in the suction tank stops them before they run dry. Part 3 covers these, with the high-level alarm and backup float valve above the stop point.
  • Booster sets follow pressure. When a tap opens and the pressure falls below the "cut-in" setting, a pump starts. When the pressure rises to the "cut-out" setting and the flow stops, the pump stops.

The low-level cut-out and the high-level alarm are what we call interlocks, safety signals that override the normal controls. Many buildings have them, and haven't tested them since the day the building was handed over.

Short-cycling

And when those signals go wrong, one of the first things we see is short-cycling. That's a pump starting and stopping again and again over a short time, sometimes several times a minute. It always has a cause.

On a booster set, the usual cause is a pressure vessel that has lost its air cushion. Without air, the vessel can't store water under pressure. So the smallest draw makes the pressure fall, and a pump starts, runs for a few seconds and stops. Other causes are:

  • A leaking non-return valve that lets water flow backwards between starts.
  • Cut-in and cut-out pressures set too close together.
  • A pump much bigger than the building's real demand.

On a transfer pump, rapid starting usually means the start and stop probes are set too close together. That often happens after they're rehung during a tank cleaning. Where float switches are used instead, it can mean a float swinging in rough water.

Short-cycling doesn't show on the water bill, but it still costs money. Each start draws a large burst of current, heats the motor windings, and wears the contactors, bearings and seals. So a pump designed for a few starts an hour that's doing forty won't reach its design life.

The night pattern

Now let's use the pumps as a health check. The best time is at night, when an office is almost empty, so let's compare three nights of the transfer pump in our tower.

Three charts of roof tank level and transfer pump running from midnight to 6am: a normal night with one short pump run, a night with water leaving above the tank where the pump starts seven times, and a night where the stop signal has failed so the pump never stops and the tank sits at overflow level

Illustrative nights in the office tower. One run is normal, and many runs mean water is leaving. A pump that never stops, with the tank at overflow, means the stop signal has failed.

A. A normal night. Very little water is used, so the roof tank level falls slowly. The pump starts once or twice to fill it again.

B. Many more starts than usual. Each run moves about the same volume, the water between the start level and the stop level. So more starts means more water is leaving the roof tank, because something downstream of the tank is drawing water.

It might be a leak on the riser or floor pipes, or a stuck flush valve or tap. Or it might be an honest night user, such as cooling tower make-up while the air-conditioning plant runs.

If we know the volume between the start and stop levels, the number of starts tells us about how much water went. So a pump that used to start twice a night and now starts seven times is worth a closer look.

C. The pump never stops, and the roof tank is overflowing. Remember from Part 3 that an overflowing tank is at its highest level. So a working stop probe would already have stopped the pump, and here the stop signal has failed.

It might be a fouled or disconnected stop probe, a stop probe rehung too high after cleaning, or a panel left in manual mode. The backup float valve on the inlet has failed to shut too.

From the ground floor, night C looks perfectly fine. Taps work and tenants are happy, while treated water runs from the roof tank overflow into the drain all night.

And the building pays to pump every litre of it up 80 metres. This fault can go on for months, because nobody in the offices hears a roof tank overflow.

Two other patterns are worth knowing.

The pump never stops, but the tank isn't overflowing. If the level is steady just above the high-level alarm, the stop signal has probably failed and the backup float valve has shut. Now the pump is running against a closed valve, which heats the pump and can damage it.

The high-level alarm should have gone off. But if the level is low or falling while the pump runs, the pump is delivering less than the building draws. Look for a worn pump, a partly closed or choked valve, or a large leak on the rising main.

The suction tank overflows. This is a different fault. The suction tank is filled by mains pressure through its own float valve (Part 3). So the transfer pumps can look normal while the suction tank's float valve lets water run to the overflow.

A booster set that never stops follows the same logic. With no one drawing water, holding pressure should need almost no flow. So if a pump keeps running or restarting all night, the zone is losing water somewhere, or a valve is passing.

Pumping lost water

So when a leak or overflow happens above the transfer pumps, what does it cost? The building pays for the water, and it also pays for the electricity to lift it.

Lifting one cubic metre of water 50 metres takes about 0.14 kWh of hydraulic work, which is the energy that ends up in the water.

Worth knowing: a kilowatt-hour, kWh, is the unit of energy on an electricity bill. Power vs Energy in the Electricity Fundamentals course explains it.

Real pumps and motors lose some energy as heat, though. With a combined efficiency of about 50 to 60 per cent, typical for an older set, that becomes about 0.2 to 0.3 kWh. That's what the switchboard supplies for each cubic metre lifted 50 metres.

These are illustrative figures, because the real number depends on the lift, the pipe sizes and the pump's condition.

Our tower lifts water about 80 metres. That takes about 0.22 kWh of hydraulic work per cubic metre, or about 0.4 kWh from the switchboard at the same efficiency.

Now suppose 780 m³ a month is lost somewhere above the transfer pumps, say through stuck flush valves. That's the same size of loss as the float valve example in Part 3:

  • Electricity: 780 × 0.4 is about 310 kWh of extra pumping energy a month.
  • Water: 780 m³ of water bought and lost, plus part of the sewerage charge, which is also based on water use.

So the pumping cost is real. But for most buildings the water itself costs far more. When Part 7 prices a cubic metre, the water and sewerage come to several ringgit, while lifting it takes well under one kWh.

A stop failure like night C usually wastes much more, because the pump's full flow goes to the drain until someone fixes it. And the pumps wear out faster moving water that nobody uses.

Four signals to watch

So how do we keep an eye on all this without living in the pump room? Four signals cover most pump problems:

  1. Running hours for each pump show whether the duty pump is being swapped.
  2. Starts per hour catch short-cycling before it damages a motor.
  3. Tank level catches a failed stop signal, a stuck float valve and an overflow.
  4. Flow at night shows water leaving when the building should be almost empty.

Most pump panels already show the first two, on a counter or in the building management system. Tank level needs a continuous level sensor.

Night flow needs a meter that records readings through the night, ideally after the tanks, and Part 10 explains how to read it.

Optional detail: where the figures in this part come from.

  • SPAN's Uniform Technical Guidelines for Water Reticulation and Plumbing (April 2018, section C.3.5) set the eight-hour roof tank filling time. They also cover the hydro-pneumatic or variable speed booster set, and generator backup for pumps in buildings other than landed houses.
  • The same guideline sets minimum efficiencies for booster pumps. It's 45 per cent for pumps below 10 m³/h, and 50 per cent for 10 to 30 m³/h.
  • The hydraulic work figure is mass × gravity × height. So 1,000 kg × 9.81 m/s² × 50 m is about 0.49 MJ, or 0.14 kWh.

The water itself

So we've now followed the water from the street into the suction tank, up to the roof and down to every floor. We've seen the tanks that store it, the pressure that moves it and the pumps that lift it. But we haven't looked at the water itself.

After all that storing and pumping, is it still as safe as when it left the treatment plant? And whose job is it to keep it that way? That's Part 5: Keeping Stored Water Safe in Buildings.

Check your understanding

1. At 3am the transfer pump in the office tower is running and the roof tank is overflowing. The pump panel shows no fault. What has failed?

Show the answer

The tank is at its highest level, so a working stop probe would have stopped the pump. So the stop signal has failed, for example a fouled or disconnected stop probe, or the panel left in manual.

And the backup float valve on the inlet isn't shutting either. Water is running to the drain while the building pays to pump it 80 metres up.

2. The booster set for levels 19 and 20 starts every few seconds through the night, even though nobody is using water. What is the most likely cause?

Show the answer

A pressure vessel that has lost its air cushion. It can no longer supply small draws, so the pressure drops as soon as anything draws water.

A leaking non-return valve, or cut-in and cut-out settings that are too close together, can cause the same pattern. If the pump is also delivering water steadily, check for a leak or a passing valve in the zone.

Recap

  • A pump adds pressure, which lifts water and overcomes friction in the pipes.
  • Transfer pumps fill the roof tanks and follow the tank level. Booster sets hold a pressure and follow a pressure switch or sensor, often with a pressure vessel and a variable speed drive.
  • Pumps come in duty and standby sets, and they should share the running hours.
  • Short-cycling usually means a waterlogged pressure vessel, a leaking non-return valve, or start and stop settings too close together.
  • More transfer pump starts at night means something downstream of the roof tank is drawing water. A pump that never stops while the roof tank overflows means the stop signal and the backup float valve have failed.
  • Wasted water costs both water charges and pumping electricity, and the water usually costs more.

This is Part 4 of 12 in Cobler's Water Fundamentals course. Previous: Water Tank Level Control in Buildings. Next: Keeping Stored Water Safe in Buildings.

Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.

FAQ

Frequently asked questions

Ask us about this topic

Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.

0/500

Keep reading