Blog
Why Air Conditioning Is the Biggest Line on a Malaysian Building's Electricity Bill
In a Malaysian building, cooling is often over half the electricity bill. Follow the ringgit to see why the chiller wins over lights, lifts and plug loads.

Part 14 of 20 in Cobler's Cooling Fundamentals course. New here? See the course page.
The office tower uses about 500,000 kWh of electricity a month. Now imagine we could split that bill by what used the power, such as the lifts, the lights, the computers and the cooling. Which line would be the biggest?
In an air-conditioned Malaysian office, it's the cooling, by a long way. As a typical range, the air conditioning share of building electricity is about 40 to 60%. Lighting, lifts, computers, signage and everything else share the rest.
The exact share depends on how the building is used, how many hours it runs, and how much IT or process load it carries. So let's see why cooling takes so much and how it shows up on a TNB (Tenaga Nasional Berhad) bill. Then we'll see which changes to try first.
The biggest load
Let's start with our two buildings. In the office tower, the chiller plant alone, meaning the chillers, pumps and cooling towers, uses about 35% of the building's electricity.
The air handling unit fans and lobby fan coil units that move the cooled air add about another 10%. So air conditioning as a whole is about 45%. In the shoplot, with its split units and cassettes and a café on the ground floor, air conditioning is about 45% of its electricity too.
But why is cooling so big? In this climate, it's the one load we can't switch off and still use the building. We can dim the lights, put computers to sleep and take the stairs.
But if we stop removing heat and moisture from an occupied room, the room becomes unusable within an hour or so. So cooling runs whenever the building is open, and often a little before and after.
Humidity and no cool season
There are two more reasons cooling's share is higher here. The first is humidity. As Part 3 explained, cooling has two jobs, lowering the air temperature (sensible load) and removing moisture (latent load).
In a dry climate the air arrives with little moisture, so the latent load is small. In Malaysia it's large, and it never stops. Every drop of water from a fan coil drain pan, or a split unit's drain pipe, is moisture taken out of the air. And condensing it took electricity.
The second reason is that Malaysia has no heating season, and no mild months when the cooling plant can coast. Chillers and aircon units run all year, with no seasonal shutdown.
A building in a four-season country can leave much of its cooling plant idle for months. Here, the compressors work every operating day of the year. When a building is empty, the usual energy-saving step is to let the cooling setpoint drift up, so the plant works less hard.
So put the three facts together. It's a large load, with a heavy humidity job, running all twelve months, and that's why cooling takes the biggest share of the annual bill.
The biggest load first
Because cooling is such a large share, a modest percentage improvement in cooling saves more energy than a large improvement on a smaller load. Say cooling is 55% of your bill and lighting is 12%:
- Improve cooling by 10%, and you cut 10% of 55% = 5.5 percentage points off the total bill.
- Improve lighting by 30%, and you cut 30% of 12% = 3.6 percentage points off the total bill.

A 10% gain on a 55% share saves more than a 30% gain on a 12% share, because the percentage acts on a bigger base.
So the much bigger gain on lighting still saves less, because it acts on a smaller base. That's no argument against efficient lighting, which is usually cheap and easy. It's an argument about order, so when time and budget are limited, look at the largest load first.
And Part 13's kW per ton lets us put a number on a cooling gain. The office tower's plant runs at a measured 0.95 kW/RT against a design target of 0.85 kW/RT.
The plant uses about 35% of 500,000 kWh a month, which is 175,000 kWh. Reaching the target would cut plant electricity by (0.95 − 0.85) ÷ 0.95, about 10.5%. That's about 18,400 kWh a month for the same cooling.
Energy and demand
Now, what does all that cost? That depends on how the bill charges for it. The bill uses both kilowatts (kW, the rate at which we use energy) and kilowatt-hours (kWh, the total energy used).
Worth knowing: if that difference is new to you, read power vs energy: kW and kWh explained first. Your TNB Bill, Line by Line explains the full bill, as part of our Understanding Your Electricity Bill course.
A non-domestic TNB bill has several lines. Two of them depend on how we use electricity, and cooling affects both. Here we'll keep to the figures we need for cooling:
- Energy (kWh): the total electricity used in the month. Under RP4, the TNB tariff structure in force since July 2025, it's charged per kWh on every non-domestic tariff.
- Maximum demand (kW): the highest metered 30-minute average power drawn in the month. For how the meter records it, see how electricity meters work.
Whether maximum demand costs money depends on the tariff:
- Medium-voltage (MV) tariffs charge a capacity charge and a network charge for each kW of maximum demand. On MV non-domestic General, these are RM29.43/kW and RM59.84/kW, RM89.27/kW together, and the highest half hour counts at any hour of any day.
- On MV non-domestic ToU (time of use), they're RM30.19/kW and RM66.87/kW, RM97.06/kW together. But only demand inside the 2pm to 10pm, Monday to Friday peak window is charged.
- Low-voltage (LV) tariffs have no per-kW demand charge. They charge capacity and network per kWh instead, at 8.83 sen/kWh and 14.82 sen/kWh on LV non-domestic General. So a small shop or shoplot on LV pays for cooling through its kWh only.
The office tower is on MV General. In September 2026, its maximum demand was 1,600 kW, so its capacity and network charges were 1,600 × RM89.27 = RM142,832. On this tariff, each kilowatt of avoidable peak costs RM89.27 a month.
When cooling sets the peak
Cooling often sets the month's maximum demand. The chillers are the largest load, and they work hardest at the same times of day as everything else.
The office tower's maximum demand is usually set on a hot weekday afternoon, between 2:30pm and 3:00pm. That's when the chillers are close to full load.
So what would the plant's target efficiency be worth here? At 0.85 kW/RT, the plant would draw up to about 90 kW less at its afternoon peak of about 900 RT. That's 900 × 0.95 = 855 kW, against 900 × 0.85 = 765 kW.
On MV General, that could be worth up to about 90 × RM89.27, which is about RM8,000 a month. But that's only if the peak half hour falls by the same amount.
Another common peak is the morning start. After a warm weekend, the building has soaked up heat. So on Monday morning, several chillers, pumps and air handlers start together to bring the space down to setpoint.
The plant draws hard for a short time. How much that matters depends on the tariff:
- On MV General, a Monday-morning spike can set the month's maximum demand, because demand counts at any hour. So staggering equipment starts is worth checking.
- On MV ToU, a spike at, say, 8am is outside the 2pm to 10pm window, so it isn't charged as demand. The peak that matters is in the afternoon and evening.
- On an LV tariff, there's no demand charge, so the spike doesn't change the bill directly. Only the kWh used counts.
Worth knowing: to estimate what your own peak costs, the maximum demand calculator gives a rough figure. Treat it as a first estimate, not a diagnosis.

Which half hour sets the demand charge depends on the tariff. It's any half hour on MV General, but only the weekday 2pm to 10pm window on MV ToU.
There's also a bigger engineering answer to the peak, called thermal energy storage, or peak shaving. Some plants make chilled water or ice overnight and store it in an insulated tank. They use it during the day, so fewer chillers run in the expensive hours.
On MV ToU, that lowers demand in the peak window. It also moves kWh to the cheaper off-peak energy rate, which on TNB's RP4 MV ToU tariff is 27.23 sen/kWh against 31.32 sen/kWh peak.
On MV General, where the energy rate is the same at any hour, the benefit comes mainly from a lower maximum demand. Storage needs space and careful design, though, and this course doesn't cover it further.
The setpoint
But the cheapest change in the building is the number on the thermostat. As a rule of thumb, each 1 °C you raise the cooling setpoint saves a few percent of cooling energy.
A warmer target means the plant removes less heat, and the temperature difference it works against is smaller, so the compressors run less.
That's why the usual advice is to aim for about 24 °C in occupied spaces, not 20 °C. At 20 °C, people reach for jackets indoors while the plant uses extra electricity to keep them cold.
At 24 °C, most people are comfortable in normal office clothes. And the change costs nothing, takes seconds, and can be reversed if people complain.
For the shoplot, the setpoint is the main lever too. Its air conditioning uses about 45% of 8,000 kWh, which is 3,600 kWh a month.
On LV General, every kWh costs 27.03 sen for energy, 8.83 sen for capacity and 14.82 sen for network. Add 3.67 sen of AFA, the Automatic Fuel Adjustment for September 2026, and that's 54.35 sen in all.
So the shoplot's air conditioning costs about 3,600 × 54.35 sen, about RM1,960 a month. Each percent saved is worth about RM20 a month.
Full load is rare
So cooling is the biggest line on the bill, and kW per ton is how we grade the plant behind it. But there's a catch in that grade. A chiller's nameplate kW per ton is measured at full load, and a chiller hardly ever runs at full load.
So what's its efficiency the rest of the time? That's Part 15: Why Chiller Efficiency Is Measured at Part Load.
Check your understanding
1. Cooling is 50% of a bill and lighting is 10%. Which saves more, a 10% gain on cooling or a 40% gain on lighting?
Show the answer
The cooling gain. 10% of 50% is 5 percentage points of the bill. The lighting gain is 40% of 10%, which is 4 percentage points.
2. Your chillers start together at 7:30am every Monday and set a high spike. Does it raise your demand charge?
Show the answer
It depends on the tariff. On MV General, yes, if it's the highest half hour of the month, because demand counts at any hour.
On MV ToU, no, because only demand between 2pm and 10pm on weekdays is charged. And on an LV tariff, there's no per-kW demand charge at all.
Recap
- In an air-conditioned Malaysian building, cooling typically takes about 40 to 60% of the electricity, driven by humidity and a climate with no cool season.
- Because cooling is the largest load, a modest cooling gain beats a large gain on a small load.
- Cooling affects the kWh on the bill. On MV tariffs, it also affects the capacity and network charges set by the highest 30-minute demand.
- Those are RM89.27/kW on MV General, at any hour, and RM97.06/kW on MV ToU, in the weekday 2pm to 10pm window. LV tariffs charge them per kWh instead.
- Raising the setpoint towards 24 °C is the cheapest first step.
Go deeper on video (optional)
This video shows how a building's chillers, air handling units and rooftop units work together, which is why central cooling is the largest electrical load. It doesn't cover TNB tariffs, and you won't need it for the next part.
This is Part 14 of 20 in Cobler's Cooling Fundamentals course. Previous: COP, EER and kW per Ton: How to Read Chiller and Aircon Efficiency Numbers. Next: Why Chiller Efficiency Is Measured at Part Load: Understanding IPLV.
Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.
FAQ
Frequently asked questions
As a typical range, air conditioning takes about 40 to 60% of the electricity in an air-conditioned Malaysian office, making it the largest single load. Lighting, lifts, IT equipment and other plug loads share the rest. The exact share depends on how the building is used, its operating hours and how much IT or process load it carries.
Two reasons. First, there is no cool season, so chillers and aircon units run year-round with no seasonal shutdown. Second, our humid air adds a large latent load, the energy needed to condense water vapour out of the air. That comes on top of the sensible load of lowering the temperature. A dry climate has little moisture to remove. A tropical one removes it every operating hour.
As a rule of thumb, each 1 °C higher on the cooling setpoint saves a few percent of cooling energy. The plant removes less heat, and the compressors run less. Setting occupied spaces to about 24 °C instead of 20 °C is comfortable in normal office clothes and costs nothing to try.
Ask us about this topic
Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.


