Blog

COP, EER and kW per Ton: How to Read Chiller and Aircon Efficiency Numbers

COP, EER, CSPF and kW/ton all grade one thing: cooling delivered per unit of electricity. Learn to read each one and honestly grade your own chiller plant.

Tan Kok XinTan Kok XinCooling Fundamentals
Illustration of two cooled rooms linked to a meter panel that compares energy in with cooling out

Part 13 of 20 in Cobler's Cooling Fundamentals course. New here? See the course page.

Picture two identical offices side by side, both held at 24 °C on a hot afternoon. They feel exactly the same.

But one building's cooling might be using far more electricity than the other's to deliver that comfort. We can't feel the difference, and the thermostat won't show it.

So how do we compare two cooling machines fairly? We need a number that divides the cooling delivered by the electricity used.

There are four versions of that number you'll meet, called COP, EER, CSPF and kW per ton. So let's take them one at a time, and then grade the office tower's plant.

Cooling out, electricity in

Every one of these numbers answers the same question. How much cooling does this machine deliver for each unit of electricity it uses?

And here's something that looks odd at first. A good chiller delivers five or six units of cooling for every unit of electricity.

If you think of efficiency as "output can never be more than input", that looks impossible. An electric heater, for example, turns 1 kW of electricity into 1 kW of heat and can go no higher.

But a cooling machine doesn't turn electricity into cold. As we saw in Part 1, it moves heat out of the building. The electricity runs the compressor, fans and pumps that do the moving.

The heat that's moved isn't made from the electricity, so there's no rule that says it must be smaller. Moving heat takes less energy than the amount of heat moved. So a ratio of 5 or 6 is normal, and it breaks no law of physics.

COP

The simplest measure is the coefficient of performance (COP):

$$\text{COP} = \frac{\text{cooling output}}{\text{electrical input}}$$

Both quantities are in the same unit, kilowatts of cooling over kilowatts of electricity, so COP is a plain number with no unit. It means the same thing in every country:

  • A COP of 3 means 3 kW of heat moved for every 1 kW of electricity.
  • Higher is better.
  • A small split air conditioner typically sits around COP 2.3 to 3.5.
  • A large, well-run water-cooled chiller reaches COP 5 to 6 or better.

Why do chillers do so much better? Mainly because they reject heat through water and a cooling tower, which can cool the condenser towards the outdoor wet-bulb temperature. A small outdoor unit has to reject its heat into the hotter outdoor air.

Worth knowing: Part 8 compared air-cooled and water-cooled plant, and Part 12 showed how the tower does it.

EER

The energy efficiency ratio (EER) measures the same thing, cooling out over electricity in, but in mixed units. It divides cooling in BTU per hour (British thermal units per hour, an imperial unit of heat flow) by electrical input in watts.

Because of the mixed units, EER gives numbers such as 10 or 12. So we can't read it as a plain multiple the way we read COP. One watt is about 3.412 BTU per hour, so the two convert like this:

$$\text{COP} \approx \frac{\text{EER}}{3.412}$$

So an EER of 12 is about COP 3.5. EER is also a snapshot, measured at one fixed test condition, with one outdoor temperature and one load.

But real weather changes all day, and that's why seasonal ratings exist.

CSPF and the star label

A single snapshot can flatter a machine, because efficiency changes with the outdoor temperature and with how hard the unit is working. A seasonal rating averages efficiency across a realistic spread of conditions, so it better reflects a full cooling season.

In other countries you'll see SEER (seasonal energy efficiency ratio) for this. But on the energy label of a split unit sold in Malaysia, you won't see SEER.

Suruhanjaya Tenaga (the Energy Commission) runs the Minimum Energy Performance Standards (MEPS) scheme, and its label shows:

  • a star rating, up to 5 stars, where more stars means more efficient, and
  • a CSPF figure, the cooling seasonal performance factor. It's the cooling delivered across a season divided by the electricity used, based on a warm, cooling-only climate like ours.

So when you compare split units for a shop, office or home, use the 5-star MEPS label and its CSPF. Don't use a SEER figure from an imported catalogue.

COP and EER help us understand the physics, but stars and CSPF are what to compare when buying a unit.

kW per ton

Walk into a plant room, though, and engineers rarely say "COP". They say kW per ton (kilowatts per refrigeration ton), which this course writes as kW/RT. You'll also see it written kW/ton, as in the formula below.

It turns the ratio upside down:

$$\text{kW/ton} = \frac{\text{electrical kilowatts drawn}}{\text{tons of cooling delivered}}$$

Now the electricity used is on top and the cooling delivered is on the bottom, the opposite of COP. So for kW/RT, lower is better, because the goal is fewer kilowatts of electricity for each ton of cooling.

It's like a car's fuel use in litres per 100 km, where a smaller number means less fuel for the same distance. In the same way, a smaller kW/RT means less electricity for the same cooling.

Part 5 defined the refrigeration ton, 1 RT = 3.517 kW of cooling, and that one fact links kW/RT and COP exactly:

$$\text{COP} = \frac{3.517}{\text{kW per ton}}$$

Here's what that gives for some common values:

kW per ton (kW/RT)

COP

0.50

about 7.0

0.59

about 6.0

0.80

about 4.4

0.95

about 3.7

1.00

about 3.5

A higher COP and a lower kW/RT both mean the same thing, which is better. And this conversion catches a common mistake.

If a table calls 0.5 kW/RT "excellent" and then praises COP 4.4 as top-tier, the two scales have been mixed up. That's because 0.5 kW/RT is COP 7, while COP 4.4 is 0.80 kW/RT.

Scale showing kW per ton from 0.5 to 1.2 above the matching COP values from 7.0 to 2.9, with arrows showing lower kW per ton and higher COP are both better

The same efficiency on two scales: kW per ton falls as COP rises, using COP = 3.517 ÷ kW per ton.

What the kW counts

The kW in kW/RT is real power, the same kW that the meter records and TNB (Tenaga Nasional Berhad) bills. Power vs energy: kW and kWh explains the difference between that rate and the kWh we use over time.

Chiller compressors, pumps and fans are driven by motors. A motor's current isn't perfectly in step with the voltage, so its power factor is below 1.

A low power factor raises the current and the kVA the supply has to carry. But it doesn't raise the real kW the motor uses to do its work, and the kW, kVA and kVAR power triangle explains why.

So a low power factor doesn't make kW/RT worse, and correcting the power factor doesn't make it better in any noticeable way. To improve kW/RT, the plant has to move the same heat with less real power. That means cleaner heat exchangers, better water temperatures and better control.

Worth knowing: a low power factor can still cost money through a separate TNB surcharge. But that's an electrical supply issue, not a cooling efficiency one.

Chiller or whole plant

The most common mistake with these numbers is mixing up the chiller with the plant. A chiller's nameplate might say 0.55 kW/RT, but that counts only the electricity used by the chiller itself, mostly its compressor.

A complete water-cooled plant also runs:

  • chilled water pumps, which push cold water to the air handlers,
  • condenser water pumps, which push warm water to the cooling towers,
  • cooling tower fans, and
  • other smaller auxiliaries.

Add those in, and a plant whose chiller alone reads 0.55 kW/RT might run at 0.75 to 0.85 kW/RT as a whole plant.

The whole-plant figure is the one that matters for the electricity bill, because we pay for every one of those motors, not only the compressor. When you quote or compare a figure, always say which one it is.

Plant diagram with a small dashed box around the chiller labelled chiller only 0.55 kW per ton and a larger box around the chiller, pumps and tower fans labelled whole plant 0.75 to 0.85 kW per ton

A chiller-only figure counts one machine. A whole-plant figure also counts the pumps and tower fans that the bill pays for.

Grading the office tower

So how good is good? Here are rough grades for a water-cooled chiller plant in our climate, keeping the two kinds of figure apart:

  • A modern chiller on its own can run near 0.5 to 0.6 kW/RT (COP about 5.9 to 7.0) at its rated conditions. For comparison, 1970s-era equipment sat closer to 0.9 kW/RT for the chiller alone.
  • A good whole plant built around such a chiller typically lands around 0.75 to 0.85 kW/RT (COP about 4.1 to 4.7).
  • An average whole plant, typical of older or loosely tuned systems, sits around 0.9 to 1.0 kW/RT (COP about 3.5 to 3.9).
  • A whole plant above about 1.1 kW/RT (COP below about 3.2) is using a lot more electricity than it should, so investigate it.

The office tower has a design target of 0.85 kW/RT for the whole plant. Its measured figure is 0.95 kW/RT, which is COP 3.517 ÷ 0.95, about 3.7. That puts it in the "average" band, with room to improve.

At its peak cooling load of about 900 RT, 0.95 kW/RT means the plant draws about 900 × 0.95 = 855 kW. At the design target, it would draw about 765 kW for the same cooling.

Air-cooled plant and small split units sit higher on the kW/RT scale, because they don't have a cooling tower. For the shoplot, with its split units and cassettes, a unit around COP 3 to 3.5 is respectable for its type.

So if you look after a building like the shoplot, the star label and CSPF are the numbers to use. The whole-plant grades here apply to chilled water buildings.

The nameplate is a best case

Every efficiency figure printed for a machine, whether COP, EER, CSPF stars or kW/RT, is measured in a test lab under set conditions. That means a stated load, clean coils, set water or air temperatures and new parts.

Your plant on a humid afternoon will usually do worse, with fouled tubes, chillers at part load and pumps at full speed whatever the demand. So the nameplate tells us what the machine achieved in the test, not what it achieves every day in our building.

The only way to know a plant's real kW/RT is to measure the electricity going in and the cooling coming out. Then we follow that figure over months. Part 16 shows how to measure both.

What it costs

So now we can read any efficiency figure and say whether it's good. But what do all those kilowatts cost? Cooling uses a lot of electricity, and on a big building's bill it shows up in more than one place.

So how big is cooling's share of a Malaysian building's electricity bill? That's Part 14.

Check your understanding

1. A chiller is rated at 0.70 kW/RT. What is its COP, and is a higher or lower kW/RT better?

Show the answer

COP = 3.517 ÷ 0.70, which is about 5.0.

For kW/RT, lower is better, because electricity used is on top of the ratio. For COP, higher is better.

2. A contractor says your chiller is "0.55 kW/RT", but the plant sub-meter shows the plant using about 0.85 kW for every ton of cooling. Who is wrong?

Show the answer

Possibly neither. The 0.55 is probably a chiller-only figure at test conditions.

The 0.85 is a whole-plant figure that includes the chilled water pumps, condenser water pumps and tower fans. And the whole-plant figure is the one your bill follows.

Recap

  • COP, EER, CSPF and kW/RT all measure the cooling delivered for each unit of electricity.
  • COP is a plain ratio, and higher is better. EER is the same idea in mixed units at one test condition (COP ≈ EER ÷ 3.412).
  • CSPF and the Suruhanjaya Tenaga star rating are the seasonal figures to use when buying a split unit in Malaysia.
  • kW/RT puts electricity on top, so lower is better. It converts with COP = 3.517 ÷ kW per ton.
  • The kW is real power, so power factor doesn't change it.
  • Always say whether a figure is chiller-only or whole-plant, and remember that nameplate figures are best cases.

Go deeper on video (optional)

This video works out the savings from replacing a chiller, with COP, kW/ton and EER, and also IPLV and NPLV, which Part 15 explains. It may use US units in places, but the conversions above still apply. You won't need it for the next part.

This is Part 13 of 20 in Cobler's Cooling Fundamentals course. Previous: How Does a Cooling Tower Work? Throwing a Building's Heat at the Sky. Next: Why Air Conditioning Is the Biggest Line on a Malaysian Building's Electricity Bill.

Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.

FAQ

Frequently asked questions

Ask us about this topic

Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.

0/500

Keep reading