Blog
Why Chiller Efficiency Is Measured at Part Load: Understanding IPLV
Why a chiller's full-load nameplate number lies, and how IPLV blends part-load efficiency into one honest figure that reflects how chillers really run.

Part 15 of 20 in Cobler's Cooling Fundamentals course. New here? See the course page.
Every chiller comes with a headline efficiency figure on its nameplate, something like 0.60 kW/RT. But that figure is measured at full load, with the chiller delivering 100% of its rated cooling on a design day.
And most of the time, a chiller runs well below that. Even at the office tower's peak of about 900 RT, its two duty chillers are only at 90% load. On most hours they run lower. So what does a chiller actually achieve on all those other hours?
We'll build on Part 13, with kW/RT (lower is better) and COP (higher is better).
Worth knowing: if your building only has split units and cassettes, like the shoplot, you can skim this part. The idea that efficiency changes with load applies to your units too, but IPLV and chiller staging belong to chilled water plants.
Part load
Full load means the chiller is producing all the cooling it was designed for. Part load means it's producing less, for example 60% of its capacity on a mild, cloudy morning instead of 100% on a very hot afternoon.
A chiller is sized for the worst case, the hottest, fullest hour of the year, so the building still stays cool on that afternoon. Every other hour, the building needs less cooling than the chiller can give, so the chiller turns itself down. And oversizing, which is common, pushes it further down still.
That's where the office tower's 90% comes from. The tower has three 500 RT chillers, two on duty and one on standby, so it has 1,000 RT of duty capacity. Its peak cooling load is about 900 RT, so even at that peak, the two duty chillers sit at 90% load.
How the hours are weighted
So how much time does a chiller actually spend at each load? The AHRI 550/590 standard, the North American rating standard most of the industry uses for chillers, weights a chiller's operation like this:
- 100% load: about 1% of the time
- 75% load: about 42% of the time
- 50% load: about 45% of the time
- 25% load: about 12% of the time
So in this weighting, the full-load condition on the nameplate counts for about one hour in a hundred.
Now, these percentages are the standard's weighting assumptions, not a measured duty cycle for your building. AHRI chose them so every manufacturer calculates the same blended figure in the same way, and the results can be compared fairly.
Your building's real profile might lean heavier or lighter, depending on its occupancy, its use and the local climate. In Malaysia, where the cooling load never switches off, the profile looks different again from a temperate office block.
But the main point holds everywhere. Part-load hours dominate, and full load is rare. That means part-load efficiency decides most of your real energy use, and a single full-load figure leaves most of it out.
IPLV
So how do we turn those four load points into one number we can compare? That's what IPLV (integrated part load value) does, as defined in AHRI 550/590.
It takes the chiller's efficiency measured at four load points, 100%, 75%, 50% and 25%, and combines them into one figure using those weights.
Think of a student's grade-point average. Instead of judging the student on one exam, each subject counts according to its weight. In the same way, IPLV judges the chiller on all four load points, not only on full load.
How we combine the four results depends on which efficiency unit we use. If the four results are in kW/RT, the standard uses this form:
$$\text{IPLV} = \frac{1}{\dfrac{0.01}{A} + \dfrac{0.42}{B} + \dfrac{0.45}{C} + \dfrac{0.12}{D}}$$
Here, A, B, C and D are the chiller's kW/RT at 100%, 75%, 50% and 25% load. And 0.01, 0.42, 0.45 and 0.12 are the weights from the list above.
If the four results are COP (or EER, where higher is better), the standard uses a plain weighted sum:
$$\text{IPLV} = 0.01A + 0.42B + 0.45C + 0.12D$$
Now A, B, C and D are the COP values at 100%, 75%, 50% and 25% load.
Why two forms? The standard averages the cooling delivered per unit of electricity at each load point, which is what COP measures. So COP values can be weighted and added directly.
But a kW/RT value is the upside-down version of that ratio. So the kW/RT form first turns each value upside down (0.01 ÷ A and so on) and adds them with their weights. Then the "1 ÷" at the front turns the total back into kW/RT.
Both forms give the same answer once we convert between kW/RT and COP, and two rules follow:
- Use one unit throughout. A, B, C and D must all be kW/RT, or all COP. Mixing units gives a meaningless number.
- Use the matching formula. The reciprocal form is for kW/RT only. Putting COP values into it, or adding kW/RT values with the plain weighted sum, gives the wrong result.
A worked IPLV
Let's try it. Suppose a water-cooled chiller measures:
- A = 0.60 kW/RT at 100% load
- B = 0.55 kW/RT at 75% load
- C = 0.52 kW/RT at 50% load
- D = 0.58 kW/RT at 25% load
Notice this machine is more efficient in the middle of its range than at full load. We'll see why in a moment. Using the kW/RT form:
$$\text{IPLV} = \frac{1}{\dfrac{0.01}{0.60} + \dfrac{0.42}{0.55} + \dfrac{0.45}{0.52} + \dfrac{0.12}{0.58}} \approx 0.54 \ \text{kW/ton}$$
Working it through, 0.01 ÷ 0.60 = 0.017, 0.42 ÷ 0.55 = 0.764, 0.45 ÷ 0.52 = 0.865 and 0.12 ÷ 0.58 = 0.207. These add up to about 1.853, and 1 ÷ 1.853 is about 0.54 kW/RT.
We can check that with the COP form. Converting each point with COP = 3.517 ÷ kW/RT gives COPs of about 5.86, 6.39, 6.76 and 6.06.
The weighted sum is 0.01 × 5.86 + 0.42 × 6.39 + 0.45 × 6.76 + 0.12 × 6.06, about 6.5. And 3.517 ÷ 6.5 is about 0.54 kW/RT, the same answer.
So the full-load nameplate says 0.60 kW/RT, a COP of about 5.9. But the IPLV of about 0.54 kW/RT, a COP of about 6.5, better reflects a typical year under the standard's assumptions.

The example chiller's kW/RT at each load point, with the AHRI weight for each. The 75% and 50% points carry most of the weight.
You'll also meet NPLV (non-standard part load value). It uses the same method, but at your site's own conditions, such as your actual condenser water temperatures, instead of AHRI's standard ones. IPLV is the catalogue figure for comparing machines, and NPLV is the figure for your plant.
So two chillers with identical full-load nameplates can have very different IPLVs. Judged on its nameplate alone, our example chiller would look worse than it is. So compare chillers on IPLV, or on NPLV at your own site's conditions.
Condenser relief
You might expect a chiller at part load to waste energy, like an idling car engine. But often the opposite is true, and many chillers have a lower (better) kW/RT at 50 to 75% load than at 100%. The reason is the temperature of the condenser water.
As we saw in Part 2, the compressor takes heat from the cold side, the chilled water. It lifts that heat to the warm side, the condenser, where the cooling tower carries it away.
The bigger the temperature gap between the two sides, the higher the pressure the compressor has to lift the refrigerant to. And the higher that lift, the more electricity it uses for each ton of cooling.
Now, a chiller is usually at part load because the day is milder. And on a milder day, the cooling tower can often send back cooler condenser water.
Cooler condenser water means a smaller lift, so the compressor does the same cooling with less electricity. We call this condenser relief. The AHRI part-load test points also assume cooler condenser water as the load falls, so condenser relief is built into a chiller's published IPLV.

The compressor lifts heat from the chilled water up to the condenser water. Cooler condenser water means a smaller lift and less electricity per ton.
But there's a limit, and it matters in Malaysia. As Part 12 showed, a tower can't cool water below the outdoor wet-bulb temperature, and here the wet-bulb stays fairly high all year.
So on a Malaysian site, the condenser water may not get much cooler at part load. Then the part-load gain can be smaller than the IPLV suggests, and that's exactly what NPLV, or a measured figure, captures.
And efficiency usually falls again at very low load. In our example, the kW/RT rose to 0.58 at 25% load, because the chiller's fixed losses are spread over much less cooling. The best region is usually the middle to upper part of the range, with cool condenser water, not the very bottom.
Turning down
So how does a chiller turn itself down? To run efficiently at part load, it has to modulate, which means adjust its capacity smoothly rather than switch on and off. There are two main ways:
- Inlet guide vanes on centrifugal chillers. These are adjustable blades that control how much refrigerant vapour enters the compressor.
- Variable compressor speed, where the compressor slows down when less cooling is needed.
Variable speed uses a variable-speed drive (VSD, also called a VFD or inverter). It changes the frequency of the supply to the motor, so the motor can run at any speed.
Worth knowing: Rectifiers and inverters explains how the drive builds that variable-frequency supply. And how electric motors work explains why motor speed follows frequency.
How much does slowing down save? Well, that depends on the machine:
- Take a fan, or a pump in a closed loop with no fixed pressure to hold. Its power falls with about the cube of speed, as Part 9 showed. At 80% speed, it needs about half the power.
- A compressor is different. It always has to lift the refrigerant from low pressure to high pressure. The size of that lift is set mainly by the chilled water and condenser water temperatures, not by its speed. So a compressor's power does not follow the cube law. A variable-speed compressor saves most when the lift is smaller too, for example when the condenser water is cooler.
That's why variable-speed chillers often post strong IPLV figures, because the standard's part-load points come with cooler condenser water. That's where variable speed pays off best, but at your site, the gain depends on how cool your condenser water really gets.
Staging
A single efficient chiller is only part of the plant, though. Most large buildings have several chillers, and the controls decide how many to run and how heavily to load each one. We call that decision staging.
Take the office tower on a mild morning, with a cooling load of about 600 RT. It has two choices:
- Run three chillers at 40% each. Each one is lightly loaded and closer to the 25% region where efficiency falls again. Some plants give each chiller its own condenser water pump and tower cell. There, the third chiller also brings its pump and tower fan into service.
- Run two chillers at 60% each. Both sit in the efficient middle of their range, and the third chiller and its helpers stay off.
The second choice delivers the same cooling with less electricity. So a plant full of efficient chillers can still be an inefficient plant if it stages them badly.
Worth knowing: Part 18 looks at oversizing, short-cycling and staging problems. And Part 19 shows how the building management system (BMS) makes staging decisions.
What the plant does today
So a chiller's real kW/RT moves with its load, with the condenser water temperature, and with the slow fouling of its heat exchangers. A nameplate or an IPLV can't tell us what our plant is doing today.
So how can we tell how well our cooling is really performing, today? That's Part 16.
Check your understanding
1. A chiller's kW/RT values at 100%, 75%, 50% and 25% load are all 0.60. What is its IPLV?
Show the answer
0.60 kW/RT. With the kW/RT form, 0.01 ÷ 0.60 + 0.42 ÷ 0.60 + 0.45 ÷ 0.60 + 0.12 ÷ 0.60 = 1.00 ÷ 0.60. And 1 divided by that gives 0.60.
The weights add up to 1, so equal values give the same value back.
2. Why might a chiller in Malaysia gain less at part load than its IPLV suggests?
Show the answer
Much of the part-load gain comes from cooler condenser water, called condenser relief, and the AHRI test points assume it.
Here the outdoor wet-bulb temperature stays high all year. So the tower may not deliver much cooler water at part load, and the gain is smaller.
Recap
- In AHRI's weighting, a chiller sees its full-load nameplate condition about one hour in a hundred.
- IPLV combines its efficiency at 100%, 75%, 50% and 25% load, with weights of 1%, 42%, 45% and 12%. With kW/RT values, use the reciprocal form. With COP values, use the plain weighted sum.
- NPLV does the same at your site's conditions.
- Part load is often more efficient because of condenser relief. But the gain depends on cool condenser water, and it fades at very low load.
- The cube law applies to fans and pumps without static head, not to compressors.
- Staging decides whether a plant keeps its chillers in their efficient range.
Go deeper on video (optional)
This video works out the savings from replacing a chiller, with IPLV, NPLV, COP, kW/ton and EER. You won't need it for the next part.
This is Part 15 of 20 in Cobler's Cooling Fundamentals course. Previous: Why Air Conditioning Is the Biggest Line on a Malaysian Building's Electricity Bill. Next: BEI Malaysia: Scoring Your Building's Cooling by Measuring It.
Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.
FAQ
Frequently asked questions
IPLV (integrated part load value, defined in AHRI 550/590) is one efficiency figure for a chiller. It combines the chiller's efficiency at 100%, 75%, 50% and 25% load, using fixed weights of 1%, 42%, 45% and 12%. With kW/ton values it uses a reciprocal formula. With COP values it is a plain weighted sum. It matters because a chiller rarely runs at full load, so the full-load nameplate figure describes a condition the machine seldom sees. IPLV is a better guide to a typical year, under the standard's assumptions.
A chiller is usually at part load on milder days, when the cooling tower can often send back cooler condenser water. Cooler condenser water means a smaller pressure lift for the compressor, so it uses less electricity per ton of cooling. This is called condenser relief, and it often gives a lower (better) kW/ton at 50 to 75% load than at 100%. The gain is smaller if the condenser water stays warm, as it can in Malaysia's high wet-bulb climate. Efficiency also usually falls again at very low load.
No. The 1% at full load, 42% at 75%, 45% at 50% and 12% at 25% are weighting assumptions built into AHRI 550/590. They exist so that everyone calculates IPLV the same way. Your building's real load profile depends on its use, occupancy and climate. What holds generally is that part-load hours dominate real operation, which is why a single full-load figure is misleading.
Ask us about this topic
Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.


