Blog

The Power Triangle: kW, kVA and kVAR

A motor draws some current that does no work, just to magnetise itself. Here is why that current lags the voltage, how kW, kVA and kVAR combine in the power triangle, why transformers are rated in kVA, and what a capacitor bank changes on the cable.

Tan Kok XinTan Kok XinElectricity Fundamentals
Beer mug with foam beside a glowing right triangle, the classic kW, kVA and kVAR power triangle analogy

Part 12 of 24 in Cobler's Electricity Fundamentals course. New here? Start with the course map.

Let's go back to the level-3 AHU (air handling unit), where the fan motor from Part 11 draws 20.4 A. But 12.0 kW at 400 V should only need 17.3 A. That extra is magnetising current, and it does no work at all.

Now let's look at the same gap from the other side. The nameplate says 400 V and 20.4 A, on three phases, so if we multiply those out we get about 14.1 kVA.

But if we meter it at full load, the meter reads about 12.0 kW. So which one is right? Well, actually both are.

The gap between them is what kW, kVA and kVAR describe. It sets the size of every cable, transformer and generator in a building. And it's what TNB (Tenaga Nasional Berhad) penalises a building for when there's too much of it.

Lagging current

So why would part of a motor's current run late? Well, a coil fights every change in its own current, and we've met both halves of this already.

In Part 6, current through a coil made a magnetic field. And in Part 7, a changing field through a coil made a voltage that pushed back against the change.

Now what happens if we put both in one coil? When the supply tries to raise the current, the growing field induces a voltage that pushes against the rise.

When the supply tries to lower it, the shrinking field pushes to keep it flowing. So a coil basically treats current like a loaded shopping trolley, slow to get going and slow to stop.

That push-back is what we call self-induction, or inductance, and it's what held a transformer's idle current to a trickle in Part 9.

On AC (alternating current), the supply keeps reversing (Part 8), so the coil's current never really catches up. In a pure coil it peaks a quarter of a cycle late.

One cycle at 50 Hz lasts 20 ms, so the current peaks 5 ms after the voltage, and we say the current lags the voltage.

So where does the energy go? Well, power at any instant is voltage times current (Part 5).

While the current grows, energy flows from the supply into the field. While it shrinks, the field hands that energy back. So over a full cycle a pure coil uses nothing, and the round trip repeats 100 times a second.

A motor is kind of part coil and part working machine, so its current has two parts:

  • A working current, in step with the voltage. It turns the shaft and leaves as motion and heat, like the current in a kettle element from Part 3.
  • A magnetising current, a quarter-cycle late. It builds the field in the motor's iron, takes it down and builds it the other way, giving the energy back each time.
Voltage and current waves with the current peaking slightly after the voltage, power factor 0.8

In a motor circuit the current peaks a little after the voltage, because part of the current goes into building and releasing the motor's magnetic field.

Now that magnetising current is large. Run a motor with nothing on its shaft and nearly all of its current is magnetising current. Yet it still draws about 30 to 60% of its full-load current (Electrical Volt).

As Part 11 noted, it stays about the same whether the shaft is busy or idle. Only the working current follows the load.

kW, kVA and kVAR

So we need three ways of counting the power in one circuit:

  • Real power, in kW (kilowatts), turns a shaft, heats an element or lights a lamp. It leaves the circuit for good, and it's what the kWh meter adds up.
  • Reactive power, in kVAR (kilovolt-amperes reactive), flows into magnetic fields and back. It does no net work, but motors and transformers can't run without it.
  • Apparent power, in kVA (kilovolt-amperes), is the effective voltage times the effective current, useful or not.

Say a load has 4 A of working current and 3 A of magnetising current. How much is in the cable? My first instinct was to add them and say 7 A, but that skips one point.

The two currents peak a quarter-cycle apart, so they're never at their peaks together, and the cable actually carries 5 A.

They combine like the two short sides of a right-angled triangle. Four squared plus three squared is 25, and the square root of 25 is 5.

Power combines the same way, and that's what we call the power triangle:

$$S = \sqrt{P^2 + Q^2} \qquad \text{power factor} = \frac{P}{S}$$

In that formula:

  • \(P\) is real power in kW.
  • \(Q\) is reactive power in kVAR.
  • \(S\) is apparent power in kVA.

So a load drawing 800 kW and 600 kVAR presents \(\sqrt{800^2 + 600^2} = 1{,}000\) kVA to the supply, where adding would have said 1,400 kVA. Its power factor is 800 ÷ 1,000 = 0.8.

Power triangle: 800 kW real power and 600 kVAR reactive power make 1,000 kVA apparent power, so power factor is 0.8

Real power and reactive power combine at right angles. So 800 kW and 600 kVAR make 1,000 kVA, and the power factor is 800 ÷ 1,000 = 0.8.

Try it

Loading the interactive

Now back to the motor from the start. Three-phase apparent power is \(\sqrt{3} \times V \times I\), with the 1.732 from Part 10, so we get 1.732 × 400 × 20.4 ≈ 14.1 kVA.

Its real power is 12.0 kW, so its power factor is 12.0 ÷ 14.1 ≈ 0.85, the figure on the nameplate. Its reactive power is \(\sqrt{14.1^2 - 12.0^2} \approx 7.4\) kVAR. So that 7.4 kVAR is Part 11's magnetising current, counted as power.

A kettle's power factor is 1.0, because all of its current does work.

Worth knowing: nameplates sometimes write power factor as "cos φ", which is the same number.

Heat and kVA ratings

So if the magnetising current gives its energy back, does it cost anything? Well, it still flows through real wire, and wire heats with the square of the current (Part 3), whatever that current is doing.

In the example above, the cable carries 5 A to deliver the work of 4 A. So it loses (5 ÷ 4)² ≈ 1.56 times as much heat as the work alone would need.

This is also why transformers and generators are rated in kVA instead of kW. Their windings heat according to the current, and the current follows the kVA.

The maker can't know the customer's power factor, so kVA is the rating that protects the machine whatever the load (Schneider Electric).

A standby generator shows both limits at once. A set sold as 1,000 kVA has windings for 1,000 kVA, but its engine is usually sized for about 800 kW.

That's 1,000 kVA at an assumed power factor of 0.8. So even a load at a power factor of 1.0 can't pull 1,000 kW from it (Toromont Cat).

And light loading makes it worse. The AHU motor runs at a power factor of 0.85 at full load.

Take the load off the shaft, though, and the working current shrinks while the magnetising current stays. Then an induction motor's power factor can drop to about 0.1 to 0.3 (Electrical Volt).

So the field's energy shuttles through every cable and transformer back to the supply, heating each one. How do we keep the field but stop the shuttle?

Well, what if something beside the motor caught that energy each time the field let it go, and handed it back?

Capacitors

Well, there's a part that does just that, and it's pretty simple to build. Take two metal plates and hold them apart with a thin insulator.

The push from Part 2 piles charge onto one plate, but the charge can't cross the gap. So energy gets stored in the electric field between the plates. That sandwich is what we call a capacitor.

Now let's put it on AC. Its current is largest when the voltage is changing fastest, as the wave crosses zero. At the voltage peak the plates are full and the current stops.

So the capacitor's current peaks a quarter-cycle before the voltage, while the coil's runs a quarter-cycle behind. That makes the capacitor basically the mirror image of a coil.

Put one near a motor, and when the motor's field hands energy back, the capacitor takes it. When the field needs energy again, the capacitor gives it back.

So with capacitors near the motors, the two swap energy between themselves, 100 times a second. The magnetising current now circulates in the short loop between them.

The motor still gets its full field, but the cable back to the supply only carries the working current, 4 A instead of 5 A.

Two rows comparing a supply cable carrying 5 A without a capacitor bank and 4 A with a capacitor bank supplying the reactive current locally

A capacitor bank next to the motor supplies its reactive current locally, so the cable back to the supply carries only the working current.

In a building this is a capacitor bank, which is a cabinet of capacitors in steps.

A power factor controller measures the power factor and switches steps in and out as motors start and stop through the day. It uses contactors, the heavy-duty relays from Part 6.

The bank changes the current, the heat and the kVA upstream of where it's connected. But it barely changes kW or kWh, because the motors do the same work as before.

TNB asks for a power factor of at least 0.85 for supplies below 132 kV, and at least 0.90 at 132 kV and above. It adds a surcharge when a site falls short (TNB power factor page).

How banks are sized and what they save is covered in Power Factor Correction: What Capacitor Banks Do.

One transformer in the office tower

Let's take the course's example office tower in Kuala Lumpur (all numbers here illustrative). It reaches its maximum demand of 1,600 kW on a hot weekday afternoon.

Two 1,500 kVA transformers share it, so take one of them at 800 kW. Most of that load is motors: chiller compressors, pumps and AHU fans.

Left to themselves they'd add about 600 kVAR, and the transformer would carry 1,000 kVA at a power factor of 0.80, below TNB's 0.85.

The current on the 400 V side follows the kVA rather than the kW:

$$I = \frac{S}{\sqrt{3} \times V} = \frac{1{,}000{,}000}{1.732 \times 400} \approx 1{,}443\ \text{A}$$

The automatic capacitor bank at the main switchboard (MSB) switches in about 260 kVAR, which leaves 340 kVAR coming from the supply. We can make a little table to compare:

One transformer at peak

Without capacitors

With 260 kVAR of capacitors

Real power

800 kW

800 kW

Reactive power from the supply

600 kVAR

340 kVAR

Apparent power

1,000 kVA

869 kVA

Current at 400 V

1,443 A

1,254 A

Power factor

0.80

0.92

Heat in windings and busbars

100%

about 76%

So the work didn't change, it's 800 kW either way, but the current did. It fell by about 190 A, close to the current of nine motors like the level-3 AHU fan.

The transformer now runs at 869 ÷ 1,500 ≈ 58% of its rating instead of 67%, with about a quarter less heat in its windings. And its power factor of 0.92, the tower's usual figure, clears TNB's threshold.

One detail catches people out. The bank sits at the MSB, so what it relieves depends on where you stand:

  • Upstream of the bank (the busbars, the transformer and TNB's network), there's less current and less heat.
  • Downstream (the cable from the MSB to each chiller), nothing changes. It still carries that chiller's full magnetising current.
  • The motor itself doesn't change either. It still builds its full field.

Where the kVA come from

So the tower can now describe everything it draws. That's 1,600 kW of work plus its motors' reactive current, about 1,740 kVA at the peak (1,600 ÷ 0.92).

But it makes none of it. Every one of those kVA was generated less than a second earlier, in a power station that may be hundreds of kilometres away. It came from machines like the ones in Parts 7, 9 and 10.

So we now have every machine of the grid, and the words to describe what flows between them. But how do they connect, from one power station to one building? That's the path we'll follow in Part 13.

Go deeper (optional)

"Power Factor Explained – Your Electricity Bill Money Drain (Reactive Power)" by The Engineering Mindset


This is Part 12 of 24 in Cobler's Electricity Fundamentals course. Previous: Electric Motors. Next: The Malaysia Electricity Grid.

Cobler builds CobiNeural, which reads kW, kVA and power factor from a building's meters as live numbers. A slipping power factor shows up before the bill does. To see it on your own site, request a demo.

FAQ

Frequently asked questions

Ask us about this topic

Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.

0/500

Keep reading