Blog
Power Factor Correction: What Capacitor Banks Do
How a capacitor bank supplies a motor's reactive current locally, raises power factor toward 1, and removes TNB's surcharge, plus the silent failure that brings it back.

Part 6 of 7 in Cobler's Understanding Your Electricity Bill course. New here? See the course page.
In the tower's plant room, next to the main switchboard, there's a tall grey cabinet labelled POWER FACTOR CORRECTION. Aina's been asked to check it regularly, but nobody has told her what it's for, or what it's worth on the bill.
Well, the cabinet holds a bank of capacitors. Power factor correction means supplying the reactive current that motors need from these capacitors, close to the motors. That way it doesn't have to come through the TNB (Tenaga Nasional Berhad) network.
The site's power factor goes up, and it stays above the level where TNB adds a surcharge to the bill. But the real power (kW) and energy (kWh) the site uses hardly change, so the energy and maximum demand charges don't fall.
Power factor
So first, what is power factor? A site draws real power (kW), which does useful work such as turning a pump. It also draws reactive power (kVAR), which builds the magnetic fields that motors and transformers need on every cycle.
Together they make the apparent power (kVA), which sets how much current the cables and transformers carry. Power factor is real power divided by apparent power (kW ÷ kVA). At 1, all the current does useful work, and at 0.80, only 80 kW of every 100 kVA does.
Motors are the main cause of a low power factor. A typical induction motor runs at about 0.85 at full load, but its magnetising current barely changes as the load falls. So a lightly loaded or idling motor can drop to about 0.15 to 0.30.
Worth knowing: the Electricity Fundamentals lesson kW, kVA and kVAR: The Power Triangle explains all of this step by step. It also shows why reactive power is needed, and why it isn't wasted energy.
The 0.85 rule
So why does TNB care? Because a low power factor means more current in its cables for the same useful work.
TNB requires customers supplied below 132 kV to keep their power factor at 0.85 or higher. That covers nearly every commercial and industrial site at 11 kV or 33 kV. At 132 kV and above, the threshold is 0.90 (TNB power factor page).
Below 132 kV, TNB's published formula works like this (TNB charges and penalties page, checked 23 September 2026):
- For every 0.01 that the power factor falls below 0.85, the surcharge is 1.5 percent.
- For every 0.01 below 0.75, the surcharge is 3 percent, added on top of the 1.5 percent steps between 0.85 and 0.75.
- The percentage is applied to the bill's energy, demand and AFA (Automatic Fuel Adjustment) charges. The retail charge and the KWTBB levy aren't part of it.
Between 0.75 and 0.85, the surcharge is:
$$\text{Surcharge} = 1.5\% \times \text{Bill} \times \frac{0.85 - \text{PF}}{0.01}$$
Here "Bill" means the energy, demand and AFA charges added together, and PF is the month's power factor.
At a power factor of 0.80, the site is five steps of 0.01 below 0.85. So the surcharge is 5 × 1.5% = 7.5% of those charges. At 0.70, it would be (10 × 1.5%) + (5 × 3%) = 30%.

The surcharge starts below 0.85 and rises faster below 0.75. The percentage applies to the energy, demand and AFA charges.
Worth knowing: TNB's published rule doesn't say how it applies to LV (low voltage) accounts, whose capacity and network charges are per kWh. So if you're on LV, like the shoplot, check your own bill.
The tower at 0.80
Now let's try it on Aina's tower. It's on the MV (medium voltage) non-domestic General tariff, and its automatic capacitor banks normally hold it at about 0.92, so it pays no surcharge.
But suppose the banks stopped working and the power factor fell to 0.80 in September 2026.
From the bill in Part 3, its energy charge (RM149,150), demand charges (capacity RM47,088 plus network RM95,744) and AFA (RM18,350) add up to RM310,332. The surcharge would be 7.5% of that, RM23,274.90 in one month.
So the cabinet's main value on the bill is a charge that doesn't appear. As long as it keeps the tower above 0.85, the surcharge line stays empty.
What power factor correction doesn't change
So does the cabinet lower anything else on the bill? You might hope it trims the maximum demand (MD) charge too, but it doesn't.
As Part 4 showed, the MV capacity and network charges are billed per kW of maximum demand. That's the rule under RP4, the tariff structure in force since July 2025.
Capacitors reduce the kVA and the reactive power, not the kW that does the work. So the tower's MD stays about 1,600 kW whether its power factor is 0.80 or 0.92.
The kWh the building uses also stay about the same, so the energy and AFA lines don't change. The only energy saving is a small cut in losses in the site's cables and transformers, because they carry less current.
What does change is the load on the site's own equipment:
Power factor | Real power (kW) | Reactive power (kVAR) | Apparent power (kVA) |
|---|---|---|---|
0.80 | 1,600 | 1,200 | 2,000 |
0.92 | 1,600 | about 682 | about 1,739 |

Correction shrinks the kVAR and kVA sides of the triangle. The kW side, which sets the maximum demand charge, stays the same.
Try it
At 0.92, the transformers and cables carry about 13 percent less current for the same work than at 0.80.
For a sense of scale, a 1,000 kVA transformer at a power factor of 0.75 can deliver only 750 kW of useful power. So a quarter of its capacity is taken up carrying reactive current, and raising the power factor frees that capacity for real load.
Capacitor banks
So how does a cabinet of capacitors do all this? A capacitor bank at the main switchboard supplies the motors' reactive current locally, so it no longer has to come through the TNB meter.
A capacitor's current leads the voltage, while a motor winding's current lags. So the reactive energy moves back and forth between the capacitors and the motors on every cycle, instead of travelling to and from the grid.
The TNB meter then sees less kVA for the same kW, and the power factor rises towards 1. The power triangle lesson shows this with a diagram.
Switching in steps
Now, you'd think one big block of capacitors would do the job. But a site's reactive demand changes through the day, and too much correction causes its own problems. That's why real banks are automatic and switch in steps.
Early in the morning, a building might run one chiller and a few pumps. Then it needs a fraction of the reactive power it needs at 2pm with the whole plant running. So a fixed block of capacitors sized for the afternoon would over-correct in the morning.
Over-correction makes the power factor leading, which means the site's current leads the voltage, and it raises the voltage on the site's switchboard. TNB publishes no surcharge for a leading power factor, but the voltage rise is a reason to avoid it.
And power factor can't go above 1.0, so rather than chase the highest figure, the aim is a controlled range, usually 0.95 to 0.98.
An automatic bank has several capacitor steps and a power factor regulator. The regulator measures the power factor all the time and switches steps in and out to follow the target as the load changes. That keeps the site above 0.85 without tipping it into a leading power factor.
Detuned banks
Sites with variable frequency drives (VFDs) need one more thing. Where there are VFDs and other electronic loads, a plain capacitor bank can amplify harmonics, so the bank is fitted with detuned reactors.
VFDs and other electronic loads draw harmonic currents at multiples of 50 Hz. Examples are the 5th harmonic at 250 Hz and the 7th at 350 Hz. Electrical Harmonics, a side reading in our Electricity Fundamentals course, explains where they come from.
A capacitor bank and the inductance of the supply together form a circuit with a natural, or resonant, frequency. If that frequency is close to a harmonic already on the busbar, the bank amplifies that harmonic instead of only correcting power factor.
Then the capacitors overheat, protection trips and the bank fails early.
A detuned bank has a reactor, which is a coil, in series with each capacitor step. The reactor is sized so that the resonant frequency sits below the lowest harmonic present.
A 7 percent reactor tunes the bank to 189 Hz, and a 14 percent reactor tunes it to 134 Hz. Both are well below the 5th harmonic at 250 Hz.
Above its tuning frequency the bank behaves like a coil, so it can't resonate with those harmonics. On most sites with VFDs, a detuned bank is the usual choice, and a harmonic measurement confirms which reactor size is needed.
Silent failures
There's one last reason Aina's been asked to check the cabinet. A capacitor bank needs maintenance, because its steps age and lose capacitance. A step can also drop out completely, for example when its fuse blows.
Worth knowing: when a capacitor step fails, nothing in the building changes. The regulator keeps switching the remaining steps, the cabinet still looks as if it's working, and the chillers and pumps run as before. The first sign is often a power factor surcharge on the TNB bill, a month or more after the failure.
So it's worth tracking power factor all the time, rather than checking it once at commissioning. A monthly look at the power factor on the TNB bill is the minimum.
An energy monitoring system that records power factor at the main switchboard shows a failing step as a downward trend. That trend appears soon after the step fails, before it reaches the bill. For more worked cases of the surcharge, see our power factor surcharge article.
The owner's question
So now Aina can explain every line on the tower's bill. The power factor of 0.92 means no surcharge, and the capacitor cabinet is worth keeping in good order. A slip below 0.85 would add 1.5% of the energy, demand and AFA charges for every 0.01.
And that brings her back to where she started, with the two questions the owner asked in her first week. She has everything she needs to answer them now. So let's sit down with her and write that answer, in Part 7: Read and Reduce Your Electricity Bill.
Check your understanding
1. A factory's power factor is 0.80. It installs a capacitor bank, and the power factor rises to 0.95. What happens to its maximum demand charge, and why?
Show the answer
Very little. Under RP4, the MV demand charges are billed per kW of maximum demand. The capacitors supply reactive power (kVAR) locally and reduce the kVA, but the kW the factory uses to do its work stays about the same.
The saving comes from removing the power factor surcharge, which is 7.5 percent of the energy, demand and AFA charges at 0.80. It also frees transformer and cable capacity.
2. Why is a real capacitor bank split into steps with a regulator, instead of one fixed block?
Show the answer
Because the site's reactive demand changes through the day. A fixed block sized for the busiest time would over-correct at quiet times, making the power factor leading and raising the switchboard voltage. A regulator switches steps in and out to keep the power factor in a target range, usually 0.95 to 0.98.
Recap
- Power factor is kW ÷ kVA, and lightly loaded motors pull it down.
- Below 132 kV, TNB adds a surcharge when power factor falls below 0.85. It's 1.5 percent of the energy, demand and AFA charges for each 0.01 below 0.85, and 3 percent for each 0.01 below 0.75.
- At 0.80, the tower would pay RM23,274.90 in September 2026.
- A capacitor bank supplies reactive current locally, so the grid carries less kVA and the power factor rises.
- Correction removes the surcharge and frees transformer and cable capacity, but it barely changes kW, kWh or the per-kW demand charge.
- Real banks switch in steps and need detuned reactors where there are VFDs. They should be monitored, because steps fail without visible signs.
This is Part 6 of 7 in Cobler's Understanding Your Electricity Bill course. Previous: Time-of-Use, Green Tariffs and Avoidable Penalties. Next: Capstone: Read and Reduce Your Electricity Bill.
Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.
FAQ
Frequently asked questions
It supplies the reactive current that motors need from capacitors at the switchboard, instead of drawing it from the grid. A capacitor's current leads the voltage while a motor winding's current lags, so their reactive currents are half a cycle apart. So the reactive energy moves back and forth between them locally. The grid then supplies less apparent power (kVA) for the same real power (kW), and the power factor rises towards 1.
TNB requires customers supplied below 132 kV to keep their power factor at 0.85 or higher. That covers nearly all commercial and industrial sites at 11 kV or 33 kV. Customers supplied at 132 kV and above must keep it at 0.90 or higher. Falling below the threshold adds a power factor surcharge to the bill.
For supply below 132 kV, TNB's published formula adds 1.5 percent for every 0.01 the power factor falls below 0.85. It adds a further 3 percent for every 0.01 below 0.75. The percentage is applied to the bill's energy, demand and AFA charges, not to the retail charge or KWTBB. At a power factor of 0.80 the surcharge is 5 × 1.5% = 7.5% of those charges. At 0.70 it is 30%. For an MV office tower whose energy, demand and AFA charges total RM310,332, a power factor of 0.80 would add RM23,274.90 in a month.
Very little. Under RP4 the medium-voltage capacity and network charges are billed per kW of maximum demand. Capacitors reduce kVA and reactive power, not the kW that does the work. The savings come from avoiding the power factor surcharge and from freeing transformer and cable capacity, plus a small reduction in cable and transformer losses.
Where VFDs and other non-linear loads produce harmonics, a plain capacitor bank and the supply's inductance can resonate near a harmonic frequency. The bank then amplifies that harmonic, which overheats the capacitors and trips protection. A detuned bank adds a reactor in series with each step, so the resonance sits below the lowest harmonic present. A 7 percent reactor tunes it to 189 Hz and a 14 percent reactor to 134 Hz, both below the 250 Hz 5th harmonic.
Yes. Too much capacitance makes the power factor leading and raises the voltage on the site's switchboard. Power factor cannot exceed 1.0, so the aim is a controlled range, usually 0.95 to 0.98. Automatic banks switch capacitor steps in and out with the load so the site stays above 0.85 without becoming leading.
Capacitor steps age and can drop out, for example when a fuse blows, without any visible sign. The regulator keeps switching the remaining steps and the plant runs normally. The power factor drifts down and the surcharge can return. Checking the power factor on every TNB bill is the minimum. An energy monitoring system that records power factor shows the drift as a trend before it reaches the bill.
Ask us about this topic
Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.


