Blog

Power Factor Correction: What Capacitor Banks Do

How a capacitor bank supplies a motor's reactive current locally, raises power factor toward 1, and removes TNB's surcharge, plus the silent failure that brings it back.

Tan Kok XinTan Kok XinUnderstanding Your Electricity Bill
Open capacitor bank cabinet beside power triangles shrinking as power factor improves toward unity

Part 6 of 7 in Cobler's Understanding Your Electricity Bill course. New here? See the course page.

In the tower's plant room, next to the main switchboard, there's a tall grey cabinet labelled POWER FACTOR CORRECTION. Aina's been asked to check it regularly, but nobody has told her what it's for, or what it's worth on the bill.

Well, the cabinet holds a bank of capacitors. Power factor correction means supplying the reactive current that motors need from these capacitors, close to the motors. That way it doesn't have to come through the TNB (Tenaga Nasional Berhad) network.

The site's power factor goes up, and it stays above the level where TNB adds a surcharge to the bill. But the real power (kW) and energy (kWh) the site uses hardly change, so the energy and maximum demand charges don't fall.

Power factor

So first, what is power factor? A site draws real power (kW), which does useful work such as turning a pump. It also draws reactive power (kVAR), which builds the magnetic fields that motors and transformers need on every cycle.

Together they make the apparent power (kVA), which sets how much current the cables and transformers carry. Power factor is real power divided by apparent power (kW ÷ kVA). At 1, all the current does useful work, and at 0.80, only 80 kW of every 100 kVA does.

Motors are the main cause of a low power factor. A typical induction motor runs at about 0.85 at full load, but its magnetising current barely changes as the load falls. So a lightly loaded or idling motor can drop to about 0.15 to 0.30.

Worth knowing: the Electricity Fundamentals lesson kW, kVA and kVAR: The Power Triangle explains all of this step by step. It also shows why reactive power is needed, and why it isn't wasted energy.

The 0.85 rule

So why does TNB care? Because a low power factor means more current in its cables for the same useful work.

TNB requires customers supplied below 132 kV to keep their power factor at 0.85 or higher. That covers nearly every commercial and industrial site at 11 kV or 33 kV. At 132 kV and above, the threshold is 0.90 (TNB power factor page).

Below 132 kV, TNB's published formula works like this (TNB charges and penalties page, checked 23 September 2026):

  • For every 0.01 that the power factor falls below 0.85, the surcharge is 1.5 percent.
  • For every 0.01 below 0.75, the surcharge is 3 percent, added on top of the 1.5 percent steps between 0.85 and 0.75.
  • The percentage is applied to the bill's energy, demand and AFA (Automatic Fuel Adjustment) charges. The retail charge and the KWTBB levy aren't part of it.

Between 0.75 and 0.85, the surcharge is:

$$\text{Surcharge} = 1.5\% \times \text{Bill} \times \frac{0.85 - \text{PF}}{0.01}$$

Here "Bill" means the energy, demand and AFA charges added together, and PF is the month's power factor.

At a power factor of 0.80, the site is five steps of 0.01 below 0.85. So the surcharge is 5 × 1.5% = 7.5% of those charges. At 0.70, it would be (10 × 1.5%) + (5 × 3%) = 30%.

Line chart of TNB power factor surcharge against power factor. It is zero at 0.85 and above, rises 1.5 percent per 0.01 to 15 percent at 0.75, then rises faster to 30 percent at 0.70. Marked points show 7.5 percent at 0.80

The surcharge starts below 0.85 and rises faster below 0.75. The percentage applies to the energy, demand and AFA charges.

Worth knowing: TNB's published rule doesn't say how it applies to LV (low voltage) accounts, whose capacity and network charges are per kWh. So if you're on LV, like the shoplot, check your own bill.

The tower at 0.80

Now let's try it on Aina's tower. It's on the MV (medium voltage) non-domestic General tariff, and its automatic capacitor banks normally hold it at about 0.92, so it pays no surcharge.

But suppose the banks stopped working and the power factor fell to 0.80 in September 2026.

From the bill in Part 3, its energy charge (RM149,150), demand charges (capacity RM47,088 plus network RM95,744) and AFA (RM18,350) add up to RM310,332. The surcharge would be 7.5% of that, RM23,274.90 in one month.

So the cabinet's main value on the bill is a charge that doesn't appear. As long as it keeps the tower above 0.85, the surcharge line stays empty.

What power factor correction doesn't change

So does the cabinet lower anything else on the bill? You might hope it trims the maximum demand (MD) charge too, but it doesn't.

As Part 4 showed, the MV capacity and network charges are billed per kW of maximum demand. That's the rule under RP4, the tariff structure in force since July 2025.

Capacitors reduce the kVA and the reactive power, not the kW that does the work. So the tower's MD stays about 1,600 kW whether its power factor is 0.80 or 0.92.

The kWh the building uses also stay about the same, so the energy and AFA lines don't change. The only energy saving is a small cut in losses in the site's cables and transformers, because they carry less current.

What does change is the load on the site's own equipment:

Power factor

Real power (kW)

Reactive power (kVAR)

Apparent power (kVA)

0.80

1,600

1,200

2,000

0.92

1,600

about 682

about 1,739

Two power triangles side by side for the example office tower. Both have the same 1,600 kW base. Before correction at power factor 0.80 the reactive side is 1,200 kVAR and the long side 2,000 kVA. After correction at 0.92 the reactive side is about 682 kVAR and the long side about 1,739 kVA

Correction shrinks the kVAR and kVA sides of the triangle. The kW side, which sets the maximum demand charge, stays the same.

Try it

Loading the interactive

At 0.92, the transformers and cables carry about 13 percent less current for the same work than at 0.80.

For a sense of scale, a 1,000 kVA transformer at a power factor of 0.75 can deliver only 750 kW of useful power. So a quarter of its capacity is taken up carrying reactive current, and raising the power factor frees that capacity for real load.

Capacitor banks

So how does a cabinet of capacitors do all this? A capacitor bank at the main switchboard supplies the motors' reactive current locally, so it no longer has to come through the TNB meter.

A capacitor's current leads the voltage, while a motor winding's current lags. So the reactive energy moves back and forth between the capacitors and the motors on every cycle, instead of travelling to and from the grid.

The TNB meter then sees less kVA for the same kW, and the power factor rises towards 1. The power triangle lesson shows this with a diagram.

Switching in steps

Now, you'd think one big block of capacitors would do the job. But a site's reactive demand changes through the day, and too much correction causes its own problems. That's why real banks are automatic and switch in steps.

Early in the morning, a building might run one chiller and a few pumps. Then it needs a fraction of the reactive power it needs at 2pm with the whole plant running. So a fixed block of capacitors sized for the afternoon would over-correct in the morning.

Over-correction makes the power factor leading, which means the site's current leads the voltage, and it raises the voltage on the site's switchboard. TNB publishes no surcharge for a leading power factor, but the voltage rise is a reason to avoid it.

And power factor can't go above 1.0, so rather than chase the highest figure, the aim is a controlled range, usually 0.95 to 0.98.

An automatic bank has several capacitor steps and a power factor regulator. The regulator measures the power factor all the time and switches steps in and out to follow the target as the load changes. That keeps the site above 0.85 without tipping it into a leading power factor.

Detuned banks

Sites with variable frequency drives (VFDs) need one more thing. Where there are VFDs and other electronic loads, a plain capacitor bank can amplify harmonics, so the bank is fitted with detuned reactors.

VFDs and other electronic loads draw harmonic currents at multiples of 50 Hz. Examples are the 5th harmonic at 250 Hz and the 7th at 350 Hz. Electrical Harmonics, a side reading in our Electricity Fundamentals course, explains where they come from.

A capacitor bank and the inductance of the supply together form a circuit with a natural, or resonant, frequency. If that frequency is close to a harmonic already on the busbar, the bank amplifies that harmonic instead of only correcting power factor.

Then the capacitors overheat, protection trips and the bank fails early.

A detuned bank has a reactor, which is a coil, in series with each capacitor step. The reactor is sized so that the resonant frequency sits below the lowest harmonic present.

A 7 percent reactor tunes the bank to 189 Hz, and a 14 percent reactor tunes it to 134 Hz. Both are well below the 5th harmonic at 250 Hz.

Above its tuning frequency the bank behaves like a coil, so it can't resonate with those harmonics. On most sites with VFDs, a detuned bank is the usual choice, and a harmonic measurement confirms which reactor size is needed.

Silent failures

There's one last reason Aina's been asked to check the cabinet. A capacitor bank needs maintenance, because its steps age and lose capacitance. A step can also drop out completely, for example when its fuse blows.

Worth knowing: when a capacitor step fails, nothing in the building changes. The regulator keeps switching the remaining steps, the cabinet still looks as if it's working, and the chillers and pumps run as before. The first sign is often a power factor surcharge on the TNB bill, a month or more after the failure.

So it's worth tracking power factor all the time, rather than checking it once at commissioning. A monthly look at the power factor on the TNB bill is the minimum.

An energy monitoring system that records power factor at the main switchboard shows a failing step as a downward trend. That trend appears soon after the step fails, before it reaches the bill. For more worked cases of the surcharge, see our power factor surcharge article.

The owner's question

So now Aina can explain every line on the tower's bill. The power factor of 0.92 means no surcharge, and the capacitor cabinet is worth keeping in good order. A slip below 0.85 would add 1.5% of the energy, demand and AFA charges for every 0.01.

And that brings her back to where she started, with the two questions the owner asked in her first week. She has everything she needs to answer them now. So let's sit down with her and write that answer, in Part 7: Read and Reduce Your Electricity Bill.

Check your understanding

1. A factory's power factor is 0.80. It installs a capacitor bank, and the power factor rises to 0.95. What happens to its maximum demand charge, and why?

Show the answer

Very little. Under RP4, the MV demand charges are billed per kW of maximum demand. The capacitors supply reactive power (kVAR) locally and reduce the kVA, but the kW the factory uses to do its work stays about the same.

The saving comes from removing the power factor surcharge, which is 7.5 percent of the energy, demand and AFA charges at 0.80. It also frees transformer and cable capacity.

2. Why is a real capacitor bank split into steps with a regulator, instead of one fixed block?

Show the answer

Because the site's reactive demand changes through the day. A fixed block sized for the busiest time would over-correct at quiet times, making the power factor leading and raising the switchboard voltage. A regulator switches steps in and out to keep the power factor in a target range, usually 0.95 to 0.98.

Recap

  • Power factor is kW ÷ kVA, and lightly loaded motors pull it down.
  • Below 132 kV, TNB adds a surcharge when power factor falls below 0.85. It's 1.5 percent of the energy, demand and AFA charges for each 0.01 below 0.85, and 3 percent for each 0.01 below 0.75.
  • At 0.80, the tower would pay RM23,274.90 in September 2026.
  • A capacitor bank supplies reactive current locally, so the grid carries less kVA and the power factor rises.
  • Correction removes the surcharge and frees transformer and cable capacity, but it barely changes kW, kWh or the per-kW demand charge.
  • Real banks switch in steps and need detuned reactors where there are VFDs. They should be monitored, because steps fail without visible signs.

This is Part 6 of 7 in Cobler's Understanding Your Electricity Bill course. Previous: Time-of-Use, Green Tariffs and Avoidable Penalties. Next: Capstone: Read and Reduce Your Electricity Bill.

Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.

FAQ

Frequently asked questions

Ask us about this topic

Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.

0/500

Keep reading