Blog
Electric Circuits and Switches
An electric circuit is a closed loop from source to load and back. Built up from Ohm's law: the switch as 0 and 1, series vs parallel, Kirchhoff's two rules, why a short circuit can draw 460 A, and how one floor's distribution board adds up its branch currents.

Part 4 of 24 in Cobler's Electricity Fundamentals course. New here? Start with the course map.
Lift the kettle from Part 3 off its base. Its element is still 17.7 Ω, and Ohm's law still says 230 V would drive 13 A through it, but now nothing flows.
A resistor does nothing until it sits in a complete path, and a building also needs a way to switch each path on and off. So what does an electric circuit actually need?
The electric circuit
Let's start simple, with a source, a load, and copper running from one to the other and back again. Current flows only while that loop is complete.
If we break it anywhere, the current stops everywhere in it at the same instant. A closed loop like this is what we call an electric circuit.
So why does it have to be a loop? Well, Part 1 showed that copper is already full of free electrons. All the source does is push the ones already in the wire, and if the path dead-ends, they've got nowhere to go.
Every working circuit has four parts:
- A source that pushes, like the 230 V from Part 2.
- A conductor going out.
- A load where the energy gets used. That's Part 3's resistance, like a kettle element.
- A return path back. At a socket, that return path is the neutral wire.
And one rule falls straight out of the loop. In a single loop the current is the same at every point, because charge can't pile up anywhere. Part 20 uses exactly this to send sensor readings down long wires without losing accuracy.
Switches
Now picture the inside of the light switch by an office door. When it's on, two metal contacts are pressed together.
When you flick it off, a spring snaps them a few millimetres apart, and that much air is plenty to stop a 230 V supply. The loop breaks and the lamp goes dark.
That's really all a switch is, a gap in the loop that we can open and close on purpose. A loop with a break in it, whether it's an open switch, a blown fuse or a snapped wire, is called an open circuit.
So a switch has exactly two states and nothing in between. Open means no current and the lamp is off, and closed means current flows and the lamp is on.
Engineers write open as 0 and closed as 1. That's the smallest piece of information there is, so small that it actually has its own name, one bit.
Worth knowing: a whole thread of this course grows from that bit. In Part 6 one circuit learns to flip another circuit's switch. In Part 15 the moving metal gets replaced by silicon, and in Part 20 measurements get written as rows of these 0s and 1s.
Where we put the switch matters too. Wiring rules put a single-pole switch in the live conductor, never in the neutral.
That way, with the switch open, the lamp holder is cut off from the live side of the supply. So the metal inside it isn't sitting at 230 V when someone changes the lamp.
The neutral is held close to earth at the supply transformer, and Part 14 explains how and why.
Series and parallel
But what happens when one supply feeds lots of loads? Think about an old string of fairy lights, where one dead bulb switched off all the others.
But in an office, one dead lamp switches off nothing else, and the kettle in the pantry keeps boiling whatever the lights are doing. It's the same copper and the same 230 V, so the difference has to be in how the paths are arranged.
In a series circuit the loads sit one after another on one loop. The same current passes through all of them, and they share the voltage.
In a parallel circuit each load sits on its own branch across the same two supply wires. Each one gets the full voltage and draws its own current.
Let's take the fairy lights first, with twenty identical bulbs in series on 230 V. In series, the resistances add up:
$$R_{\text{series}} = R_1 + R_2 + \dots \qquad I = \frac{V}{R_{\text{series}}}$$
If each bulb has a resistance of 23 Ω when it's lit, the string adds up to 20 × 23 = 460 Ω.
Ohm's law from Part 3 then gives the current, 230 ÷ 460 = 0.5 A, the same in every bulb. Each bulb has 0.5 × 23 = 11.5 V across it.
Now when one filament burns through, the only path is broken. It's an open circuit, and all twenty bulbs go dark while you hunt for the dead one.
Series wiring still has a job, though. A switch, a fuse or a breaker always sits in series with whatever it controls, so all of the current passes through it.
Now let's wire one lamp through two switches, A and B, and walk through every case. In series:
- Both open: it's dark.
- A closed and B open: it's still dark.
- A open and B closed: still dark.
- Both closed: only now does it light.
If we put the same two switches in parallel, only the first case is dark, because either switch will do. Hold onto that, because Part 6 turns it into logic.
So how does a building get away from the fairy-light problem, where one break darkens everything? Well, what if every load had its own loop, strung across the same two supply wires?
That's parallel wiring, and it's how a building connects its loads. Each branch is its own loop, so each one obeys Ohm's law on its own.
Take the pantry from Part 2, where the kettle's 17.7 Ω element draws 230 ÷ 17.7 = 13 A. The microwave draws 5.2 A, so to the supply it looks like a 44 Ω load (230 ÷ 5.2). If we switch off the microwave, the kettle still gets its full 230 V.
Now here's something that catches a lot of people out. Every branch we add lowers the total resistance the supply sees, because we've given the current one more way through:
$$\frac{1}{R_{\text{parallel}}} = \frac{1}{R_1} + \frac{1}{R_2} + \dots$$
For the kettle and microwave that works out to about 12.6 Ω, and 230 ÷ 12.6 ≈ 18.2 A, which is just 13 A plus 5.2 A. In other words, in parallel the currents add up in the wires that feed the branches.

In series, the loads share one path and the voltage. In parallel, each load has its own branch and gets the full 230 V.
Kirchhoff's rules
Kirchhoff's rules are basically two pieces of bookkeeping, and every circuit obeys them, series or parallel.
- The current rule: at any junction, the current flowing in equals the current flowing out, because charge doesn't appear or vanish at a joint. That's why the kettle's 13 A and the microwave's 5.2 A leave the supply as one 18.2 A.
- The voltage rule: around any closed loop, the pushes add up to the drops. Each charge picks up energy at the source and gives all of it away in the loads before it gets back. That's why twenty bulbs at 11.5 V each add up to exactly 230 V.
With these two rules plus Ohm's law, we can find the current in any branch of any building.
Short circuits
Now let's say someone hanging a shelf drives a screw into the pantry wall. It cuts the socket cable 25 m from the board and joins its live and neutral wires.
So the current now has a way back that skips the kettle. A path that bypasses the load like this is what we call a short circuit.
You'd probably guess that with the kettle out of the loop, less current flows. To be honest, so would I, but Ohm's law shows the opposite happens.
Normally the kettle's 17.7 Ω limits the current to 13 A. Now the only resistance left is the copper itself.
In Part 3 we worked this cable out from \(R = \rho L / A\), and 50 m of 2.5 mm² copper, out and back, comes to about 0.34 Ω. If we add an illustrative 0.15 Ω for the supply side, the whole loop is about 0.5 Ω:
$$I = \frac{230\ \text{V}}{0.5\ \Omega} = 460\ \text{A}$$
That's 35 times the kettle's current. And Part 3 showed that heating goes with the current squared (\(I^2 R\)).
So the cable now heats about 35 × 35, more than 1,200 times faster than in normal use. In well under a second, its insulation would pass its safe temperature.
So an open circuit and a short circuit are kind of opposite faults. In one, no current flows, and in the other, far too much does. Most electrical faults are one or the other.
Stopping a short is the circuit breaker's main job. A 20 A breaker of the common Type B sort trips almost instantly once the current passes 3 to 5 times its rating.
For 20 A, that's 60 to 100 A (circuit breaker types explained). Our 460 A opens it in a fraction of a second and turns the short back into a harmless open circuit. That fast trip comes from an electromagnet, which we'll build in Part 6.
Protection also comes in layers. Malaysia uses the British-style BS 1363 plug (adopted locally as Malaysian Standard MS 589). It holds a cartridge fuse, usually rated 3 A or 13 A (BS 1363).
That fuse is Part 3's deliberate weak link, and it sits in series with one appliance to protect that appliance's thin flexible cord. The 20 A breaker back at the board is too large to protect it.
Worth knowing: current leaking to earth through a metal case or a person needs different protection, which Part 14 covers.

Branch currents add up in the cable feeding the board. A short circuit bypasses the load, and the breaker opens the loop.
The distribution board
A distribution board (DB) is where a building turns one supply into lots of parallel circuits. So let's picture the DB on one floor of the office tower we've been following since Part 1, a fictional 20-storey tower in Kuala Lumpur.
Inside there's a copper bar, the busbar, carrying the supply. A row of miniature circuit breakers (MCBs) hangs off it, each one feeding its own loop out to the floor and back.
A real floor DB spreads its circuits across three phases (Part 10). Here we'll follow four circuits on one phase at 10 a.m. on a weekday, with illustrative figures.
Circuit (breaker) | What is running | Branch current |
|---|---|---|
Lighting, east wing (10 A) | 24 LED panels | 3.8 A |
Lighting, west wing (10 A) | 24 LED panels | 3.8 A |
Desk sockets (20 A) | 12 laptops and monitors | 6.5 A |
Pantry sockets (20 A) | kettle and microwave | 18.2 A |
Each branch gets the full 230 V and works on its own, so if we switch off the east-wing lights, the pantry kettle never notices.
Now let's apply Kirchhoff's current rule at the busbar. Four branch currents leave it, so the same total has to arrive through the incoming cable, which is 3.8 + 3.8 + 6.5 + 18.2 = 32.3 A.
The breaker ratings add up to 60 A, and yet only 32.3 A flows. That's because not everything runs flat out at once, and designers count on that.
And if that screw ever meets the pantry cable, the pantry breaker opens its one loop, and the lights and desks stay on. So the fault stays inside the smallest loop that contains it, which is what good design aims for.
Counting the work
By now we can find the push and the flow in every branch of an electric circuit. But we still can't say how much work got done. The floor's incomer carries 32.3 A at 230 V, and we know where each amp goes.
But a kettle drawing 13 A for three minutes and a ceiling fan drawing 0.2 A all working day both just look like "some amps".
Volts and amps alone can't tell us which one used more, and neither is what TNB, Peninsular Malaysia's electricity utility, actually bills. So how do we compare them?
Well, we need to combine volts and amps into a rate of doing work, then add that rate up over time. That's Part 5: Power vs Energy: kW and kWh.
Go deeper (optional)
This video starts exactly where this part does, with a light switch as a 0 or a 1. Then it follows that switch through relays and transistors to building controls. You don't need it for Part 5.
"Digital Electronics - The First Video YOU Should Watch" by CaptiveAire
And for the breaker letters and ratings on a real board, read circuit breaker types explained.
This is Part 4 of 24 in Cobler's Electricity Fundamentals course. Previous: Resistance and Ohm's Law. Next: Power vs Energy: kW and kWh.
Cobler's CobiNeural shows a facility team the live load on every metered board and feeder in a building. To see your own circuits as numbers, request a demo.
FAQ
Frequently asked questions
An electric circuit is a closed loop that carries current from a source, through a load that uses the energy, and back to the source. It has four parts: a source, a conductor, a load and a return path. The source can be a socket or a battery, the conductor is usually copper, and the load can be a lamp, motor or heater. At a socket, the return path is the neutral wire. Break the loop anywhere and the current stops everywhere in it, which is exactly what a switch does on purpose.
In a series circuit the loads sit one after another on one loop. The same current flows through every load, their resistances add and they share the voltage. One break stops everything, like old fairy lights going dark when one bulb fails. In a parallel circuit each load has its own branch across the same supply, so each gets the full voltage and works on its own. The branch currents add up in the feeding cable. Buildings wire their loads in parallel.
A short circuit is a path that skips the load, letting current flow almost directly from live back to neutral. With the load bypassed, only the small resistance of the wiring and the supply limits the current. By Ohm's law, 230 V across a loop of about 0.5 ohms drives about 460 A, which is about 35 times a kettle's current. The cable then heats more than 1,200 times faster than normal. A circuit breaker's job is to open the loop within a fraction of a second.
They are opposite faults. An open circuit has a break in the path, such as an open switch, a blown fuse or a snapped wire, so no current flows. A short circuit has a path with almost no resistance, so far too much current flows until a breaker or fuse opens the loop. Most electrical faults are one or the other.
So that every socket and light gets the full 230 V and each load runs independently. Switching off a lamp does not affect the kettle, and one failed appliance does not stop the others. The cost is that branch currents add up in the cable feeding them (Kirchhoff's current rule). So the incomer of a distribution board carries the sum of every circuit running at that moment. Cables and breakers are sized for that total.
Malaysia uses the British-style BS 1363 plug (adopted locally as MS 589), which holds a cartridge fuse, typically rated 3 A or 13 A. The fuse sits in series with one appliance and is a deliberate weak link that protects that appliance's own thin flexible cord. The 20 A breaker at the distribution board protects the fixed wiring in the walls. But it is rated far too high to protect a thin cord, so the plug fuse does that job.
Ask us about this topic
Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.


