Blog

Earthing and RCDs

A bird sits on an 11,000 V line unharmed because there is almost no voltage across its body. That rule explains earthing and RCDs: how fault current finds its way home, why a breaker has a thermal and a magnetic trip, and how an RCD's iron ring catches a 30 mA leak.

Tan Kok XinTan Kok XinElectricity Fundamentals
Bird perched safely on a high-voltage overhead line between insulators on a transmission tower arm

Part 14 of 24 in Cobler's Electricity Fundamentals course. New here? Start with the course map.

There's about 36,000 A waiting behind one of the office tower's transformers, ready to flow into any short circuit (Part 13). We know faults will happen, so how do we make a building's electricity safe to live with?

Well, that's the job of earthing and RCDs (residual current devices). But before we can protect a person, we need to know what a shock actually is.

Birds on power lines

Here's something that seems kind of odd. A bird can land on an 11,000 V overhead line, sit there, and fly off unharmed. And yet a person who touches the same line from the ground can be killed.

So what's different? Well, current only flows through a body when there's a voltage difference across it, and both of the bird's feet are on the same wire.

We can work it out with Ohm's law from Part 3. Say the line carries 200 A and its conductor has a resistance of about 0.1 ohm per kilometre (illustrative).

The bird's feet are 5 cm apart, so the wire between them has a resistance of 0.000005 ohm. So the voltage across the bird is 200 × 0.000005 = 0.001 V, one thousandth of a volt.

That's less than a thousandth of what one AA battery gives. Through a body of thousands of ohms, that drives almost nothing.

Now a person on the ground touching the same line is different, because their hand is at line voltage and their feet at earth. On an 11 kV line, each conductor sits about 6,350 V above earth (11,000 ÷ 1.732, from Part 10). All of it can appear across their body.

So a shock happens when current passes through the body between two points at different voltages.

That also explains what we call step voltage near a fallen line. Current spreading into the ground puts nearby points at different voltages, and a normal stride can span them. So treat every fallen line as live and stay well away.

Faults and earthing

So what do we mean by a fault? Well, a fault is current taking a path it was never meant to take. The earth wire gives that current a deliberate, low-resistance path back to the source, so the protection can see it and disconnect the circuit.

In a short circuit, live touches neutral or another phase and the current is huge (Part 4). In an earth fault, live touches something connected to earth, like a metal casing.

Take a washing machine where a damaged live wire touches its metal casing. Without an earth connection, the casing just sits close to 230 V. So anyone who touches it and an earthed tap at the same time completes a path through their body.

Equipment designed for protective earthing has its casing connected to a protective conductor, the green-and-yellow wire, which runs back to the source's earthed point. Now the fault current has its own path.

How big that current is decides how fast the circuit gets cut, and Ohm's law sets it:

$$\text{fault current} = \frac{230\ \text{V}}{\text{resistance of the whole fault loop}}$$

So the loop's resistance is what counts, and that depends on how the building is earthed. That's set by the rules of Suruhanjaya Tenaga (ST), the Energy Commission, so everything here describes practice in Peninsular Malaysia. Sabah and Sarawak have separate requirements.

  • When the protective conductor runs all the way back to the transformer, we call the arrangement TN-S. Then the loop can be as low as Part 4's 0.5 ohm (illustrative). The fault current is 230 ÷ 0.5 = 460 A, enough to trip a breaker almost at once.
  • In the TT arrangement, which the ST safety code describes as generally used, the casing connects to the building's own earth rods. The fault current returns through the soil to the earthed point at the substation of TNB (Tenaga Nasional Berhad). Say the rods measure 10 ohms and TNB's earth 1 ohm (illustrative), so 230 ÷ 11 ≈ 21 A. That's barely above a 20 A circuit's rating, so no breaker trips quickly, while the casing sits around 21 × 10 = 210 V above earth.

Now this is where my first guess about earthing went wrong. I would have said the earth rods make a fault safe by draining it away into the ground.

But the TT numbers say otherwise, because the soil holds the current to 21 A and leaves the casing at 210 V. So the earth path's real job is to carry enough current for the protection to act.

That's why a TT installation relies on an RCD for earth faults. For a consumer-owned transformer substation, like the tower's, the ST code recommends TN-S, subject to its conditions. Neutral and Earth: Why They Stay Separate (TT and TN-S) covers both in detail.

Circuit breakers

So how does a breaker know when to trip? Well, it actually has two sensors in one box. A strip of two metals, heated by the current, catches slow overloads, and an electromagnet catches sudden large faults.

  • The thermal trip is a bimetal strip, two metals bonded together that expand by different amounts when warm. The current heats it by \(I^2 R\) (Part 3), the strip bends, and past a set point it pushes the trip bar. It's slow on purpose, so a motor's starting surge doesn't trip it. A miniature circuit breaker (MCB) must trip within an hour at 1.45 times its rating, and faster as the overload grows (Schneider Electric).
  • The magnetic trip is a coil around a steel plunger, the electromagnet from Part 6. The pull grows with the current, and above a threshold the plunger snaps forward and releases the latch in milliseconds. A Type B MCB does this at 3 to 5 times its rating, a Type C at 5 to 10 times.

Every breaker on a switchboard has those two sensors, from the large air circuit breaker at the incomer to the MCBs in each distribution board. Circuit Breaker Types explains each kind.

Now let's take a 20 A Type B breaker, which trips magnetically somewhere between 60 and 100 A, and try the three cases:

  • The TN-S fault, 460 A, is far past the magnetic threshold, so it trips almost instantly.
  • The TT fault, 21 A, is below the magnetic threshold and barely over the rating, so neither sensor trips it quickly.
  • A leak through a person, say 50 mA, is a quarter of one percent of 20 A, so it's invisible to both.

So this breaker needs 60 A or more before it acts fast. How do we go from that to noticing five hundredths of an amp?

Well, what if, instead of asking how big the current is, we checked whether all of it comes back? And that's what an RCD does.

RCDs

An RCD kind of works like a doorman counting heads. Every bit of current that goes out on live should come back on neutral. If the counts differ, some has left by another route, maybe through a person.

So let's take a look inside. Live and neutral both pass through one ring-shaped iron core and act as its primary. A sensing coil wound around the ring is the secondary. So the ring is actually a transformer from Part 9, wired so that it sees nothing at all in normal use.

  • Normal use. 10 A flows out on live and 10 A comes back on neutral. Their magnetic fields in the ring are equal and opposite, so they cancel. With no changing field, nothing is induced in the sensing coil (Part 7).
  • A leak. A damaged lead lets 30 mA flow through a person to earth. Now 10.030 A goes out and only 10.000 A comes back. That 30 mA difference makes a changing field in the ring, which induces a voltage in the sensing coil. That drives a small trip coil, another electromagnet, which releases the contacts.

A general-purpose RCD rated at 30 mA must open within 300 ms at 30 mA, and within 40 ms at 250 mA (Hager). It must not trip at half its rating, 15 mA (IPD), so the small leakage of healthy equipment doesn't trip it.

Two views of an RCD. On the left, live carries 10 A out and neutral 10 A back through one iron ring, so their fields cancel and the sensing coil stays quiet. On the right, 30 mA leaks from the appliance through a person to earth, so 10.030 A goes out and 10.000 A comes back, and the leftover field in the ring drives the sensing coil and trip coil, which open the contacts.

An RCD only asks whether all the current comes back, and when 30 mA goes missing, it opens the circuit.

Now one thing to be careful about. A fast-acting RCD rated 30 mA or less adds protection against electric shock. But its rating doesn't limit the current through a person to 30 mA, and it doesn't guarantee survival.

Malaysian law (Electricity Regulations 1994, Regulation 36) sets the maximum rating for each type of final circuit. For example:

  • 10 mA where floors are likely to be wet
  • 30 mA where hand-held equipment is used
  • 100 mA for other installations, with limited exceptions

These are maximums for the designer, and never permission to bypass a device.

An RCD does have one blind spot. If a person touches live and neutral together, the current through them goes out on one conductor and back on the other. Both are inside the ring, so the RCD sees no difference.

On a board you'll find it as an RCCB (residual current circuit breaker), which needs a separate breaker for overloads. Or it's an RCBO (residual current breaker with overcurrent protection), which does both jobs in one.

Its test button makes a deliberate small leak inside the device. Use it as the manufacturer and the site procedure direct, and report it if it fails to trip. Keep in mind that a trip proves the mechanism works, but it tells you nothing about the earthing.

The shower room RCD

So let's take a look at one in the office tower (this case is illustrative). The tower has a ground-floor shower room for staff who cycle to work. Its two storage water heaters share a final circuit protected by a 10 mA RCD, the maximum allowed for a wet area.

For two weeks, the RCD tripped most weekday mornings, soon after 6:30 a.m. when a timer switched the heaters on. Each time, someone reset it and it held.

So why mornings? Well, the heater element explains the timing. It's a coil of resistance wire (Part 3) inside a metal sheath, packed in magnesium oxide powder, which blocks current but carries heat well.

If the sheath corrodes or cracks, moisture gets into the powder and its insulation resistance falls. Then the leak to the earthed sheath and tank follows Ohm's law:

$$\text{leakage current} = \frac{230\ \text{V}}{\text{insulation resistance}}$$

At 23,000 ohms, the leak is 10 mA. An RCD may trip at anything above half its rating, so a 10 mA device can trip at 5 mA. An insulation resistance of about 46,000 ohms would allow that.

And the element only leaks while it's switched on, which is why the trips followed the timer.

An electrical competent person isolated the circuit. In Peninsular Malaysia, that's someone registered with ST whose certificate covers the work. They tested the insulation resistance of each element, and one read far lower than the other. Replacing it stopped the trips.

So the trip that kept coming back was really a measurement all along. It pointed at a water heater element leaking current through damp insulation, and the RCD did its job every morning. So the fix was the element, and never a less sensitive RCD.

Loads that reshape the wave

Now every load we've protected so far, the heater element and the motor, takes TNB's sine wave as it comes. But most modern loads don't.

An LED (light-emitting diode) driver, a laptop charger and the drive on an air handling unit (AHU) fan all reshape the wave with electronics. They switch current on and off thousands of times a second.

Worth knowing: some of these loads can leak current with a steady direct-current (DC) part, which a basic RCD's ring may not detect. So circuits for drives and electric vehicle (EV) chargers use RCD types built for it.

So to reshape a wave like that, we need a switch that can flip thousands of times a second without wearing out. How do we make one? Part 15 builds it.

Go deeper (optional)

"Where Does Grounded Electricity Actually Go?" by Practical Engineering


This is Part 14 of 24 in Cobler's Electricity Fundamentals course. Previous: The Malaysia Electricity Grid. Next: Power Electronics: Rectifiers and Inverters.

Cobler builds CobiNeural, which shows a building's metered circuits as live numbers. It can alert the facility team by WhatsApp or email when a reading turns abnormal. So a pattern like a trip every morning stands out in days. To see it on your site, request a demo.

FAQ

Frequently asked questions

Ask us about this topic

Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.

0/500

Keep reading