Blog

Three-Phase Power

One phase delivers power in pulses that hit zero 100 times a second. Three-phase power sends three waves a third of a cycle apart, so the total never drops, 230 V phases give 400 V between them, and the field they make spins motors by itself.

Tan Kok XinTan Kok XinElectricity Fundamentals
Three staggered sine waves flowing into a rotating motor stator ring, illustrating three-phase power

Part 10 of 24 in Cobler's Electricity Fundamentals course. New here? Start with the course map.

Each of the office tower's transformers from Part 9 has three pairs of windings, so it sends out three live conductors instead of one.

Now if we put a meter on any one of them against neutral, we read 230 V. Between two of them, you'd probably expect 460 V, but we actually read 400 V.

Both of those come down to timing, and together they explain three-phase power, the supply that large buildings and factories use.

And there's a reason for three. One sine wave on two wires delivers power in pulses, dropping to zero 100 times a second, as the kettle in Part 8 showed.

A kettle doesn't mind, but a chiller compressor does, and big machines need something smoother.

Single-phase power

So why does a single phase pulse like that? Well, power at each instant is voltage times current, and on a single phase both of them pass through zero together.

Twice in every cycle the voltage crosses zero, the current crosses with it, and the power delivered is zero. Between those moments it climbs to twice its average.

The 3 kW kettle from Part 8 shows the pattern. It takes 6,000 W at each peak, nothing at each zero crossing, and 3,000 W on average. The power itself is actually a wave, swinging between zero and double, 100 times a second.

For a heater that's harmless, but for a motor it's a problem. A motor's turning force, which we call its torque, follows the power it receives.

So on one phase that force shoves and pauses 100 times a second. A small fan motor kind of shrugs it off. A large compressor, though, would shake its mountings and couplings, or need a heavy flywheel to even the pulses out.

Three-phase power

So how do we go from power that pulses to power that holds steady? A single wave will always pass through zero twice a cycle. Well, what if we send more than one, timed so that whenever one wave is at zero, the others are still pushing?

It starts back at the power station, where the generator in Part 7 had one coil beside a spinning magnet. So let's put three coils around the magnet instead, spaced evenly, a third of a turn apart.

The magnet passes coil 1, then coil 2, then coil 3. Each coil makes its own 50 Hz sine wave of the same size, but each peaks a third of a cycle after the last.

A cycle lasts 20 ms, so the peaks come about 6.7 ms apart. Engineers count a full cycle as 360 degrees, so we say the three waves sit 120 degrees apart.

Sending three waves like this, each a third of a cycle behind the last, is what we call three-phase power. Each wave is one phase, and the three conductors are labelled L1, L2 and L3.

Transformers carry all three down the voltage ladder, and a three-phase transformer is three pairs of windings on one core, one pair per phase.

Three voltage waves L1 L2 L3 spaced a third of a cycle apart, and below them the power of one phase pulsing to zero while the three-phase total stays steady

Top: the three phase voltages peak one after another. Bottom: one phase alone delivers power in pulses, but the three together deliver a steady total.

Now let's add up the power. Say we put one 3 kW heater on each phase. Each heater's power still swings from zero to 6,000 W, but the three take turns.

The power on each phase follows the square of its wave, and three squares spaced 120 degrees apart always add to the same total:

$$\sin^2\theta + \sin^2(\theta - 120^\circ) + \sin^2(\theta + 120^\circ) = \tfrac{3}{2}$$

We can check it at two moments:

  • When L1's voltage is at zero, L2 and L3 are each at 75% of their peak power: 0 + 4,500 + 4,500 = 9,000 W.
  • When L1 peaks at 6,000 W, L2 and L3 are each at 25%: 6,000 + 1,500 + 1,500 = 9,000 W.

The total never moves from 9,000 W. Each phase still pulses, and yet the sum stays perfectly steady. That means a motor fed from all three phases gets a steady turning force, with no flywheel needed.

Try it

Loading the interactive

Line and phase voltage

Now back to that 400 V. Why do two 230 V phases give 400 V between them? Well, the two phases never peak at the same moment in opposite directions.

The voltage between them is the difference between two waves that are out of step. For waves 120 degrees apart, that difference is \(\sqrt{3}\), about 1.73, times the voltage of one phase.

To be honest, my own first guess was 230 + 230 = 460 V, and it's the obvious one. But adding them assumes L1 sits at its top at the very moment L2 sits at its bottom. With the waves 120 degrees apart, that moment never comes.

Let's watch one instant to see it. Each phase is 230 V RMS (root mean square, the effective value from Part 8), so it peaks at about 325 V.

At one moment in each cycle, L1 is at +281.7 V and L2 is at −281.7 V. So the voltage between them is 281.7 − (−281.7) = 563.4 V.

That's the highest the difference ever gets, and 563.4 V is the peak of a wave whose RMS value is 563.4 ÷ 1.414 ≈ 398 V. In one line, that's:

$$V_{\text{line}} = \sqrt{3} \times V_{\text{phase}} = 1.732 \times 230 \approx 398\ \text{V}$$

Rounded, that's 400 V. So one supply actually gives us two voltages. We get 230 V from any phase to neutral for lights and sockets, and 400 V between phases for big machines.

That's the "400/230 V" on Malaysian low-voltage supply. Older documents say "415/240 V", which is the legacy description.

The neutral

So what does the neutral carry? In the common star arrangement, one end of each phase winding joins at a single point, and the neutral conductor runs from there.

Kirchhoff's current rule from Part 4 says the currents meeting at a point must add up to zero. And three equal currents 120 degrees apart already cancel out at every instant, so with equal loads there's nothing left over for the neutral.

Let's check one instant. Say three equal loads each draw a current that peaks at 10 A. When L1's current is at +10 A, L2's and L3's are each at −5 A, so the total is 10 − 5 − 5 = 0.

But if we unbalance it, the neutral picks up the difference. Put 30 A on L1 and 10 A on each of L2 and L3 (heater-type loads), and the neutral carries 20 A.

The heavy phase's cable and transformer winding also run hotter, and its voltage drops more than the others.

Worth knowing: the other arrangement, delta, joins the three windings end to end in a triangle, with no neutral point. A lot of motors are wound in delta and only need the three phases. The side reading Star vs Delta compares the two.
Worth knowing: electronic loads such as LED (light-emitting diode) drivers and computers draw current in short bursts. Some of those bursts actually add up in the neutral instead of cancelling, even on a balanced board, and Part 16 explains why.

A chiller and a balanced board

Let's see how the office tower uses all this. Its big loads take all three phases. The chiller compressors, the AHU (air handling unit) fan motors, the pumps and the lifts all connect to L1, L2 and L3 at once.

For a balanced three-phase load, the power is \(P = \sqrt{3} \times V_{\text{line}} \times I\). Real motors also draw some current that does no work, and Part 12 adds the correction for that.

Let's work one out (illustrative). A 250 kW chiller compressor at 400 V draws about 250,000 ÷ (1.732 × 400) ≈ 361 A on each of its three conductors.

The same 250 kW from a single 230 V phase would need about 1,090 A. That's as much current as about 84 of Part 2's 13 A pantry kettles switched on together.

And because a three-phase motor connects to all three phases equally, it's a balanced load by design.

The small loads get spread across the phases instead. Lights and sockets are single-phase, so each final circuit takes one phase and the neutral.

At each floor's distribution board (the DB from Part 4), the electrician shares the circuits out across L1, L2 and L3. The aim is about equal current on each, and we call this balancing the load.

On level 14 of the tower, the board might read 42 A, 38 A and 45 A (illustrative). That's close enough that the neutral only carries about 6 A.

TNB (Tenaga Nasional Berhad), the utility, does the same balancing on a bigger scale, spreading the houses along a street across the three phases.

Many homes, such as a typical terrace house, take a single phase. A shoplot with larger air-conditioning units, or any large building, usually takes all three.

That's why electric vehicle (EV) charger and solar installers ask which one a house has, because it limits what they can fit.

A safety note on wire colours. In Peninsular Malaysia, the Energy Commission's Directive 11/2026 moves wiring to the international IEC 60445 colours (Energy Commission directive). The three phases become brown, black and grey (formerly red, yellow and blue), and neutral becomes blue (formerly black), while earth stays green or green-and-yellow. New wiring and alterations may use either scheme from 1 January 2026, and must use the new colours from 1 January 2029. Black and blue have swapped roles, so never judge a conductor by its colour. Identifying and testing conductors is work for a competent person registered with the Energy Commission.

A rotating field

So three phases fix the pulsing, but they also give us something else, kind of for free. Let's take three coils and space them evenly around a ring, like Part 7's generator with the magnet taken out.

Then we feed L1, L2 and L3 into them. Each coil becomes an electromagnet, like the one in Part 6, whose strength rises and falls with its own phase.

Because the phases peak one after another, the strongest point of the combined field moves from coil 1 to 2 to 3, and round again. Nothing in the ring moves, and yet the magnetic field inside it rotates, 50 turns a second for the simplest winding.

It works like the chaser lights round a shop sign. Each bulb only brightens and dims in its own spot, yet the bright patch runs round the sign. Here the bulbs are three coils, and the bright patch is the strongest point of the field.

So what happens if we put something that can turn in the middle of that ring? The field will drag it round, which is exactly what a motor needs, so let's build one in Part 11: Electric Motors.

Go deeper (optional)

This animated video shows the three phase voltages and how they combine. You don't need it for Part 11.

"How Three Phase Electricity works - The basics explained" by The Engineering Mindset

To follow the three phases from the main switchboard down to each floor, read MSB, SSB and DB.


This is Part 10 of 24 in Cobler's Electricity Fundamentals course. Previous: Transformers. Next: Electric Motors.

Cobler's CobiNeural shows a facility team live readings from every metered board, phase by phase. To spot an unbalanced board before its neutral runs hot, request a demo.

FAQ

Frequently asked questions

Ask us about this topic

Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.

0/500
Electricity Fundamentals · Part 10 of 24All 24 parts

Keep reading