Blog

How a BMS Runs the Air Side: VAV, Static Pressure Reset and Fresh Air

How a BMS delivers cooling to each zone with VAV boxes, static pressure reset and CO2-based fresh air control — the control side of comfort and air quality.

Tan Kok XinTan Kok XinBuilding Automation & BMS Fundamentals
Illustration of a supply fan and duct feeding VAV boxes above a meeting room with a CO2 sensor

Part 13 of 16 in Cobler's Building Automation and BMS Fundamentals course. New here? See the course page.

On level 12, a meeting room gets stuffy every afternoon as people arrive. A few metres away, a corner desk always feels too cold. Both are cooled by the same chiller plant, so how does each one get its own share?

In Part 12, the plant made the chilled water. Now we follow it into AHU-12A, and on into the rooms.

The BMS (building management system) runs this "air side" of the building. It controls the fans, chilled water valves and air dampers in the air handling units, fan coil units and zone boxes.

The goal is enough cool, dry air and enough fresh air in every space, without the fans working harder than they need to.

One stream of cold air

The chilled water travels from the plant to every air handling unit (AHU) in the building. An AHU is a large box with a filter, a coil full of chilled water and a supply fan. The fan pushes air across the cold coil and out into the ducts.

The Cooling course explains the machines themselves, and here we look at how the BMS controls them.

The office tower has two AHUs on most floors, and AHU-12A serves the east half of level 12. Its seven points from Part 3 cover:

  • the supply and return air temperatures
  • the filter differential pressure
  • the chilled water valve
  • the supply fan speed
  • the fan's run command and status

The first job is to make the air cold. The BMS compares the supply air temperature with its setpoint, and opens or closes the chilled water valve to hold it there. That's the supply air loop from Part 5.

In VAV systems the supply air setpoint is typically around 13 °C, and AHU-12A's sequence in Part 6 uses 14 °C.

The coil also dries the air. When humid air touches the cold coil, some of its moisture condenses into water and drains away. In Malaysia that matters a great deal, and we'll come back to it further on.

As we go, we'll add to AHU-12A whatever each control idea needs:

  • a duct static pressure sensor on the AHU
  • a temperature sensor and damper in each zone
  • for fresh air control, an outdoor air damper with a carbon dioxide (CO2) sensor

VAV boxes

So AHU-12A sends one stream of 14 °C air into a duct that branches to every zone on the floor. But the zones need different amounts.

A meeting room with twelve people and a projector needs a lot of cooling, and the empty office next door needs almost none. If both got the same airflow, one would be stuffy and the other would be cold. That's our meeting room and our corner desk.

One older answer was to send a constant airflow everywhere, then reheat the air for rooms that needed less cooling. In a tropical office, that means paying to cool the air and then paying again to warm it back up. So ordinary offices here don't reheat for comfort.

Worth knowing: some hospitals, laboratories and cleanrooms do reheat on purpose, because they must control humidity very closely.

The usual answer in modern offices is variable air volume (VAV). The supply air stays at a fairly steady cold temperature, and each room gets a different amount of it.

Each zone has a VAV box. That's a short section of duct with a damper, a blade that swings to open or close the duct, like a butterfly valve for air.

A small actuator moves the damper, as in Part 2. The box has its own controller, which reads the zone's temperature sensor:

  1. The room gets warmer than its setpoint, so the controller opens the damper and more cold air flows in.
  2. The room cools to its setpoint, so the controller closes the damper back towards a minimum airflow.
  3. The minimum keeps some air moving, so the room still gets fresh air.

Try it

Loading the interactive

VAV static pressure reset control

But opening a damper only helps if there's enough pressure in the duct to push air through it. So the BMS holds a static pressure in the main duct. Static pressure is the push behind the air, like water pressure in a pipe.

A pressure sensor sits partway down the main duct, and the BMS changes the supply fan's speed to hold that pressure at a setpoint.

Now think about a late afternoon when the load drops. Rooms reach their setpoints, and their VAV dampers close towards minimum. With less air able to escape, the pressure in the duct rises, so the BMS slows the fan to bring it back down.

That saves some energy. But say the setpoint is fixed at a value chosen for the hottest, busiest day. Then the fan still pushes hard against a row of nearly closed dampers.

So what if the setpoint itself could come down? That's static pressure reset. The BMS reads how far open every VAV damper is:

  1. If no damper is close to fully open, no zone is short of air. So the BMS lowers the pressure setpoint a little, and the fan slows.
  2. If some dampers are nearly fully open and still asking for more air, those zones are short. So the BMS raises the setpoint a little.
  3. It repeats these small steps every few minutes. The setpoint settles at the lowest pressure that still keeps every zone supplied.
AHU-12A supplies a duct with a static pressure sensor and three VAV boxes. The BMS reads the damper positions and lowers the pressure setpoint when no damper is nearly fully open

Static pressure reset: the BMS reads every VAV damper and moves the duct pressure setpoint down until one zone is only just satisfied.

One zone can spoil all of this. If a VAV box is stuck, undersized or has a faulty sensor, its damper stays fully open and keeps asking for more air.

Then the reset never lowers the setpoint. Commissioning and trend reviews (Part 8) look for a zone like that.

Fan speed and power

So why does it matter if the fan turns a little slower? Fans follow three rules called the affinity laws, which hold in ideal conditions:

  • airflow changes in proportion to fan speed
  • pressure changes with the square of speed
  • power changes with the cube of speed

The cube is what makes speed so valuable. At 80% speed, the ideal power is 0.8 × 0.8 × 0.8 = 0.51 of full power.

So in the ideal case, slowing a fan to about 80% speed cuts its power draw by about half. Airflow drops by only 20%.

A real fan doesn't follow the ideal curve all the way down, for two reasons:

  1. The duct needs a minimum pressure at the far end, so the fan can't slow as freely.
  2. The motor and its drive become a little less efficient at low speed.

So the real saving at 80% speed is up to about half, and usually less. It's still large, and fans run for thousands of hours a year.

Chart of fan power against fan speed. The ideal cube-law curve falls to 51 percent power at 80 percent speed. An illustrative real-system curve sits above it, showing a smaller saving

The ideal cube law gives about half the power at 80% speed. A real duct system with a minimum pressure saves less.

As an illustration, say AHU-12A's fan draws 6 kW at full speed. In the ideal case, 80% speed would need about 0.51 × 6 kW, or about 3.1 kW. The real figure would sit somewhere between that and 6 kW.

The fan is driven by a three-phase motor through the variable speed drive (VSD) from Part 2. The BMS sends the drive a speed signal, and the drive makes the motor follow it.

Supply air temperature reset

So that's the airflow. Can the same trick work on temperature? Making cold supply air takes cold chilled water, and colder water costs the chiller more energy, as we saw in Part 12.

Say every VAV damper on the floor is sitting part-open, and no zone is struggling. Then the air is colder than the zones need.

Supply air temperature reset lets the BMS raise the supply air setpoint by a degree or two, while it watches that no zone falls behind. For AHU-12A that might mean from 14 to 15 or 16 °C. Warmer supply air lets the chilled water system work less hard.

But there are two limits:

  • Fan energy. Warmer air carries less cooling per cubic metre, so each room needs more airflow to stay cool. That asks more of the fan, which works against the static pressure reset. So a good sequence balances the two resets, instead of pushing either one to its limit.
  • Humidity. A warmer coil takes out less moisture. In Malaysia's humid air, raising the supply air temperature too far can leave rooms at the right temperature but feeling damp. So if space humidity rises towards its upper limit, the BMS stops raising the supply air temperature.

Part 2 gave the acceptable humidity range, 40 to 70% relative humidity, with many designs aiming for 50 to 60%.

Fresh air and CO2

So far, the AHU has been cooling the same indoor air over and over. But people need fresh outdoor air, to keep the space from feeling stale and to dilute the carbon dioxide we breathe out. So the AHU mixes in some outdoor air through an outdoor air damper.

In Malaysia, outdoor air is hot and very humid, and every cubic metre that comes in must be cooled and dried. So fresh air is a steady energy cost whenever the building is occupied.

The energy used to cool the air is the sensible load. The energy used to condense water out of it is the latent load, and in our climate the latent load is large. The Cooling course lesson on sensible heat, latent heat and dew point explains both.

So how much outdoor air should come in? Too little, and the air goes stale. Too much, and we pay to cool and dry outdoor air for rooms that may be half empty.

The older approach fixed the outdoor air damper at a position sized for a full house. Then the building paid for that much fresh air even at 9 a.m. on a quiet Monday.

Demand-controlled ventilation (DCV) sets the amount from the number of people. The BMS can't easily count people, but it can measure something they produce, which is CO2. Each person breathes out CO2, so indoor CO2 rises and falls with occupancy.

ICOP IAQ 2010, from the Department of Occupational Safety and Health (DOSH), uses an indoor CO2 ceiling of 1,000 ppm (parts per million). That's an indicator of whether ventilation is working.

To use DCV, AHU-12A would gain two points. One is a CO2 sensor, in the space or in the return duct, and the other is a control signal to the outdoor air damper. Then:

  1. As the floor fills and CO2 rises towards the sequence's limit, below 1,000 ppm, the BMS opens the damper wider.
  2. As people leave and CO2 falls, the BMS closes the damper back towards a minimum position.
  3. The minimum stays even when the floor is nearly empty, because people aren't the only source of indoor pollutants.

So the fresh air follows the actual number of people, instead of a guess made at design time.

And at normal office levels, CO2 does little harm by itself. What makes it useful is that it shows whether the fresh air supply is keeping up with the people in the room.

The 1,000 ppm figure is a ventilation check, not a complete air quality test. A room can be under 1,000 ppm and still have other air quality problems.

There's a bigger idea hiding in DCV, too. A CO2 sensor on the wall that tells you how stuffy a room is does monitoring, because it measures a condition.

Turning that reading into an action, such as opening the outdoor air damper or speeding up the fan, is control. The sensor observes, and the BMS decides and moves something.

So a wall display showing CO2 and humidity is a gauge. It becomes control only when a system is wired and programmed to act on the number. That's worth checking whenever someone says a space "has IAQ control".

The same difference explains why some comfort complaints go unsolved for months. "It feels stuffy in the afternoon" has no number attached. So nobody can tell whether the cause is ventilation, humidity or a zone that's short of air.

Continuous measurement of CO2, temperature and humidity turns the complaint into a trend someone can look at. Part 16 comes back to this difference between control and measurement.

Fan coil units and constant-volume AHUs

VAV is common in larger modern offices. But many Malaysian buildings, and many spaces inside VAV buildings, use simpler systems.

The office tower's ground-floor lobby and café use fan coil units (FCUs). An FCU is a small unit with a fan, a chilled water coil and a filter, usually in the ceiling of the room it serves. The Cooling course compares AHUs and FCUs.

FCU control is simpler than VAV:

  • A thermostat, usually on the wall or reading the return air, compares room temperature with its setpoint.
  • It opens or closes a two-way valve on the chilled water coil. Many FCUs use a simple open/closed valve with a small deadband, as in Part 4.
  • The fan runs at a speed the occupant or the BMS selects, often one of three fixed speeds.
  • Many FCUs have stand-alone thermostats with no BMS connection. When the thermostats are networked, the BMS can switch the FCUs on a schedule and limit how low occupants can set them. It can also see which ones are running.

A constant-volume AHU has a fan that runs at one speed, though it may have a drive that was set once at commissioning. With the airflow fixed, the BMS has only the chilled water valve to control. It can control on either of two temperatures:

  • Return air temperature, which is close to the average room temperature. This holds the rooms at setpoint, but at light load the valve closes and the coil warms up.
  • Supply air temperature, which keeps the coil steadily cold. This keeps drying the air, but on a mild day the rooms may get too cold unless the setpoint is reset.

The humidity problem is the same for FCUs and constant-volume AHUs. When the cooling load is light, the valve throttles back, the coil gets warmer, and it takes out less moisture. The room can then sit at 24 °C and still feel clammy.

People often turn the setpoint down, which overcools the room without fixing the moisture. A better sequence keeps the coil cold enough to dry the air.

It uses a humidity sensor, or a lower limit on coil or supply air temperature. Then it lets the room temperature move within that limit.

System

What the BMS varies

What it controls on

In the office tower

VAV AHU with VAV boxes

Fan speed, supply air temperature, each zone's airflow

Duct pressure, supply air temperature, each zone's temperature

Office floors (AHU-12A)

Constant-volume AHU

Chilled water valve only

Return or supply air temperature

Not used, common in older buildings

Fan coil unit

Chilled water valve (often open/closed), fan speed setting

Room or return air temperature

Lobby and café

The demand charge

So now the cold water from Part 12 becomes cold, dry, fresh air in every room. And the fans run no harder than they need to.

The air side is where most of the building's fan energy goes. The chiller plant is where most of the rest of the cooling energy goes. Together, they're the largest part of the building's electricity demand on a hot afternoon.

And on the office tower's tariff, the single busiest half hour of the month costs real money. So how can a BMS trim the building's demand for a few minutes at a time, to lower that monthly demand charge? That's Part 14: How a BMS Guards Your Electricity Bill.

Check your understanding

1. On a quiet afternoon, every VAV damper on level 12 is between 30% and 60% open. What should static pressure reset do, and why does it save energy?

Show the answer

No damper is close to fully open, so no zone is short of air. The BMS should lower the duct pressure setpoint in small steps, and the fan will slow down.

Fan power falls about with the cube of speed, so even a modest speed cut saves a large share of fan power. It's less than the ideal cube law suggests, but still large.

2. The lobby FCU holds 24 °C, but people say the lobby feels clammy. Why can this happen, and what would help?

Show the answer

At light load, the FCU's valve throttles back or stays closed for longer, so the coil is warmer and takes out less moisture. The room reaches its temperature setpoint while the humidity stays high.

Keeping the coil cold enough to dry the air, for example with a humidity sensor or a limit on coil temperature, deals with the moisture. Lowering the thermostat setpoint only overcools the room.

Recap

  • The AHU makes one stream of cold, dry air by holding a supply air temperature with its chilled water valve.
  • VAV boxes share that air out, by opening and closing a damper for each zone.
  • Static pressure reset lowers the duct pressure setpoint until one zone is only just satisfied.
  • Fan power falls steeply with speed, by up to about half at 80% speed.
  • Supply air temperature reset eases the chiller, but must respect humidity.
  • Demand-controlled ventilation uses CO2 to match the fresh air to the number of people.
  • FCUs and constant-volume AHUs control only the water valve, so the main risk at light load is poor drying.

Go deeper on video (optional)

This video walks through the VAV box and static pressure loop described above, with a duct pressure sensor driving the supply fan's drive. It's optional, and you don't need it for the next part.

This is Part 13 of 16 in Cobler's Building Automation and BMS Fundamentals course. Previous: How a BMS Optimises the Chiller Plant: Staging and Temperature Reset. Next: How a BMS Guards Your Electricity Bill: Load Shedding and Demand Limiting.

Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.

FAQ

Frequently asked questions

Ask us about this topic

Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.

0/500

Keep reading