Blog

How Does a Cooling Tower Work? Throwing a Building's Heat at the Sky

How a cooling tower rejects a building's heat by evaporating water, why range and approach grade it, and how Malaysia's humid wet-bulb sets a cold-water floor.

Tan Kok XinTan Kok XinCooling Fundamentals
Illustration of rooftop cooling towers releasing warm vapour into the air

Part 12 of 20 in Cobler's Cooling Fundamentals course. New here? See the course page.

Up on the office tower's roof sit three large boxes. They have fans on top, water splashing inside, and a faint warm mist rising from them.

Many people assume these are "the air conditioning". But no cold air comes out of them, and there's no refrigerant inside.

So how does a cooling tower work? It takes the warm water from the chillers, lets a small part of it evaporate into the outdoor air, and sends the rest back cooler.

The heat that evaporation carries away is the heat the building collected from its rooms, plus the heat added by the chillers' own electricity. The tower is where all that heat finally leaves the building.

The office tower's three cooling towers serve its three 500 RT water-cooled chillers.

Worth knowing: if your building uses split units or cassettes, like the shoplot, or air-cooled chillers, there's no cooling tower. The outdoor units give their heat straight to the air with fans, so you can skip this part.

The end of the loop

In Part 8 we followed the loops of a water-cooled plant. The chilled water loop carries cold water into the building to collect room heat.

The condenser water loop carries that heat away from the chiller to be released outside, and the cooling tower sits at its far end. So the heat travels like this:

  • The rooms give their heat to the chilled water, at the coils in the AHUs and FCUs.
  • The chiller takes that heat, plus the heat from its own compressor's electricity, and passes it to the condenser water. Part 1 explained why the heat released outdoors is always more than the heat taken from the rooms.
  • The condenser water, now warm, is pumped up to the cooling tower.
  • The cooling tower evaporates a small part of that water. The heat leaves with the vapour, and the cooled water flows back to the chiller to collect more.

So the water going up to the tower is warm, and the water coming back is cooler. The difference is heat that has left the building and gone into the outdoor air.

Evaporation

Inside the tower, the warm condenser water is sprayed over stacks of plastic sheets called fill. The fill spreads the water into thin films and slow drips, so as much water surface as possible meets the air.

A large fan draws outdoor air through the wet fill, and as the air passes the water, a small part of the water evaporates. The energy needed to change that water to vapour comes from the water left behind, so the remaining water gets cooler.

It's the same trick as the swimming pool in Part 2, or sweat on your skin. When sweat evaporates, it takes heat with it, and you feel cooler. A cooling tower uses that same effect on the building's condenser water.

Cross-section of a cooling tower: warm condenser water is sprayed over the fill, a fan draws outdoor air up through it, cooled water collects in the basin and returns to the chiller, with make-up water in and blowdown out

Warm water is sprayed over the fill while the fan draws outdoor air through it. A small part evaporates and the rest falls, cooler, into the basin.

You'd think a tower would have to evaporate a lot of water to cool the rest. But it only needs a small fraction, and two properties of water show why:

  1. Evaporating 1 kg of water, about 1 litre, takes about 2,400 kJ of heat.
  2. Cooling 1 kg of water by 1 °C releases about 4.19 kJ, the same figure we used in Part 9.
  3. Take 100 kg of warm water and evaporate 1 kg of it. The 2,400 kJ needed comes from the other 99 kg.
  4. The 99 kg cools by 2,400 ÷ (99 × 4.19) ≈ 5.8 °C.

So evaporating about 1% of the water cools the remaining 99% by around 5 to 6 °C.

And the "steam" we see above a tower is the warm, damp air the fan pushes out. Some of its moisture condenses into mist as it meets cooler air, so that mist is the building's heat on its way out.

Try it

Loading the interactive

Range

So how do we judge how well a tower is doing? Engineers use two numbers. The first is range, how much the water cools as it passes through the tower:

$$\text{Range} = T_{\text{water in}} - T_{\text{water out}}$$

Say water arrives at the tower at 35 °C and leaves at 29.4 °C. Then the range is about 5.6 °C.

Range goes up and down with how hard the building is working. A packed mall on a hot afternoon gives its towers a bigger range than the same mall at dawn.

The wet-bulb floor

But how cold can a tower make the water? The limit is set by the outdoor air, through the wet-bulb temperature we met in Part 3. It's the lowest temperature we can reach by evaporating water into the air as it is.

Dry air takes up water readily, so evaporation cools well and the wet-bulb is low. In humid air, water evaporates slowly, so evaporation cools less, and the wet-bulb is close to the ordinary air temperature.

Malaysia's air is warm and very humid, so our wet-bulb temperature is high, often around 26 to 27 °C. And a cooling tower can never cool its water below the wet-bulb temperature, which is the physical floor.

That's a limit set by the climate, not a fault in the tower. An identical tower in a dry highland town would make colder water, because the air there is drier.

Approach

The second number, approach, compares the water leaving the tower with that floor:

$$\text{Approach} = T_{\text{water out}} - T_{\text{wet-bulb}}$$

If the water leaves at 29.4 °C and the outdoor wet-bulb is 26 °C, the approach is about 3.4 °C.

A small approach means the tower is getting the water close to the coldest temperature the air allows. That's the sign of a clean, correctly sized tower with good airflow.

A typical good approach is about 3 to 4 °C. Add that to our wet-bulb of 26 to 27 °C, and we get the coldest condenser water a real tower delivers in Malaysia. It's usually around 30 °C.

Temperature ladder: water enters the tower at 35 degrees and leaves at 29.4, a range of 5.6, while the outdoor wet-bulb is 26, an approach of 3.4, and no tower can cool water below the wet-bulb

Range is the drop from water in to water out. Approach is the gap between water out and the outdoor wet-bulb, which no tower can go below.

So a large or slowly rising approach is the warning sign. A tower with scale or slime on its fill, a weak fan or a blocked air path can't get close to the wet-bulb any more. So it returns water warmer than it should.

Nothing alarms, and the building still cools, but the chiller has to work harder, as we'll see next. In Malaysia, then, the sensible target is a small approach, held steady, because the climate doesn't allow very cold water.

Warm water and the chiller

Why does warmer tower water matter so much? Because the chiller gives its heat to the condenser water.

The cooler that water is, the lower the pressure at which the chiller's refrigerant can condense, and the less work its compressor has to do. Warmer condenser water forces the compressor to push against a higher pressure, so it uses more electricity for the same cooling.

Here's a rule of thumb. Every 0.5 °C or so of rise in the condenser water temperature costs the chiller about 1 to 2% more power for the same cooling. Chillers vary, though, so check your own machine's manufacturer curve before you rely on a number.

The effect adds up. A tower that has drifted about 2.8 °C warmer than it should be can add about 5 to 10% to the chillers' electricity. And the chillers are usually the largest load in the building.

It shows up as a higher bill, not as a fault alarm, and that's why a slowly rising approach is worth watching. The reverse holds too. Keep the tower clean and its approach small, and the chiller gets the coldest water the climate allows.

Fans and water

A tower uses electricity for its fan, which is driven by a large electric motor, a significant load in its own right. Many plants put that motor on a variable speed drive (VSD). Then the fan can slow down when the day is cooler or the load is light.

Worth knowing: the Electricity Fundamentals course explains how electric motors work, and how a drive varies their speed in Power Electronics: Rectifiers and Inverters.

A tower also uses water, because evaporation is how it works. The lost water is replaced all the time by make-up water, and it leaves the tower in three ways:

  • Evaporation, the loss we want, which is the water that carried the heat away.
  • Drift, fine droplets carried out of the tower by the fan, kept small by baffles called drift eliminators.
  • Blowdown, water drained off on purpose and replaced. Evaporation leaves minerals behind, so the remaining water gets more concentrated. Blowdown removes some of that concentrated water, so scale doesn't build up on the fill and pipes.

So how much water does evaporation use? We can estimate it from the heat the tower has to remove. Take the office tower at its peak cooling load of about 900 RT:

  1. Cooling delivered: 900 × 3.517 ≈ 3,165 kW.
  2. The tower also removes the heat from the chillers' electricity. A common round figure adds about a quarter, so the heat rejected is about 1.25 × 3,165 ≈ 3,960 kW.
  3. That's 3,960 kJ every second. Each kilogram, about a litre, of water evaporated carries about 2,400 kJ.
  4. So evaporation is about 3,960 ÷ 2,400 ≈ 1.65 litres every second.
  5. Over an hour, that's 1.65 × 3,600 ≈ 5,900 litres.
  6. Over a 10-hour office day at that load, it's about 59,000 litres.

A small part of the heat warms the air directly instead of evaporating water, so real evaporation is a little lower than this. But the size is right.

For a 1,000 RT plant, the same steps give about 6,600 litres an hour. That's about 160,000 litres a day if it ran at full load around the clock. So a large plant that runs hard for long hours evaporates well over 100,000 litres a day.

The office tower's sub-meter backs this up. Its towers use about 1,350 m³ (1,350,000 litres) of make-up water a month, about 61,000 litres per working day over 22 days.

That includes blowdown and drift, and the plant is below its peak for most hours, so it sits in the same range as our estimate. It also makes the cooling towers the largest water user in the building.

Worth knowing: the optional side reading on cooling tower water consumption explains how blowdown is controlled and how to meter it.

And make-up water runs all the time, out of sight. So a stuck float valve or a slow leak can waste a lot of water before anyone notices on the bill.

That makes it worth trending the make-up water meter. Check that the flow falls close to zero at night, when the chillers are off, and a hidden loss becomes an early warning.

Tower hygiene

There's one more thing about all that warm water. The water in a cooling tower basin is typically between about 25 and 45 °C, which is the range in which Legionella bacteria multiply fastest.

The tower's drift can carry these bacteria in fine droplets. People catch legionellosis by breathing in contaminated droplets, not by drinking water.

So who looks after the tower water? Under the Occupational Safety and Health Act 1994, employers have a general duty to protect the safety and health of their employees.

That duty also covers other people affected by their work, which includes visitors, tenants and neighbours downwind of the roof. In practice, the building owner or operator should have:

  • a written risk assessment and water management plan,
  • a competent water treatment contractor,
  • regular cleaning and inspection, and
  • records showing the controls were checked.

Towers left standing idle, such as a standby cell, need their own procedure. Legionella in cooling towers explains what that plan should cover.

Electricity at every stage

So we've now followed the heat all the way from the rooms to the sky. It went through the coils, the chilled water, the chiller and the cooling tower. And at every stage, something used electricity, whether a compressor, a pump or a fan.

So how much electricity does a plant use for each ton of cooling it delivers, and how do we tell if that's good? That's Part 13: COP, EER and kW per Ton.

Check your understanding

1. Water enters a tower at 34 °C and leaves at 29.5 °C. The outdoor wet-bulb is 26.5 °C. What are the range and approach, and is the tower doing well?

Show the answer

Range = 34 − 29.5 = 4.5 °C. Approach = 29.5 − 26.5 = 3 °C.

An approach of about 3 °C is within the typical good range of 3 to 4 °C. So the tower is getting the water close to the coldest temperature the air allows.

2. A new facility manager asks for the towers to deliver 24 °C condenser water on a typical Malaysian afternoon. Why isn't that possible?

Show the answer

A cooling tower can't cool water below the outdoor wet-bulb temperature, which in Malaysia is often around 26 to 27 °C.

Add a good approach of 3 to 4 °C, and the coldest water a real tower delivers is usually around 30 °C. So the realistic target is a small, steady approach.

Recap

  • A cooling tower isn't an air conditioner. It removes the building's heat, plus the chillers' own heat, by evaporating a small part of the condenser water.
  • Evaporating about 1% of the water cools the rest by around 5 to 6 °C.
  • Range is how much the water cools in the tower. Approach is how close the leaving water gets to the outdoor wet-bulb, which no tower can go below. A good approach is 3 to 4 °C.
  • Every 0.5 °C of warmer condenser water costs the chiller about 1 to 2% more power.
  • A tower uses fan electricity and a lot of water. At peak, the office tower's plant evaporates close to 6,000 litres an hour.
  • Tower water also needs a written hygiene plan to control Legionella.

Go deeper on video (optional)

This video shows the inside of a wet cooling tower with 3D models. It's optional, and you won't need it for the next part.

This is Part 12 of 20 in Cobler's Cooling Fundamentals course. Previous: What Is a VAV System? How Ducts, Dampers and Static Pressure Deliver Cool Air. Next: COP, EER and kW per Ton: How to Read Chiller and Aircon Efficiency Numbers.

Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.

FAQ

Frequently asked questions

Ask us about this topic

Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.

0/500

Keep reading