Water FundamentalsPart 8 of 12

Blog

Cooling Tower Water Consumption Explained

In most air-conditioned buildings in Malaysia, the cooling tower quietly outdraws every toilet, tap and kitchen combined. Here is where that water goes, why cycles of concentration decide how much you waste, and how make-up metering turns guesswork into a number.

Tan Kok XinTan Kok XinWater Fundamentals
Cooling Tower Water Consumption Explained - illustration

Part 8 of 12 in Cobler's Water Fundamentals course. New here? See the course page.

Step out of a swimming pool on a breezy day and you feel cold straight away. The water on your skin evaporates, and evaporation takes heat away with it.

A cooling tower uses that same trick on a large scale, and that's why cooling tower water consumption is so high. At its peak cooling load of about 900 RT, the office tower's chiller plant turns about six cubic metres of water an hour into vapour.

None of it comes back. But that's no leak, because evaporating water is exactly how the tower does its job.

If your building has no cooling tower, you can skip this part. The shoplot, for instance, is cooled by split units and cassettes.

These are direct expansion (DX) systems, where each outdoor unit rejects its heat to the air with a fan and uses no water. Buildings on district cooling have no tower of their own either. So go straight to Part 9, because its water balance works without a tower.

In buildings with a water-cooled chiller plant, the cooling tower is usually the largest single water user on the incoming meter. It's ahead of the toilets, the kitchen and the landscaping.

Part 7 priced each cubic metre the office tower buys, and almost half of them go to its towers. Some of that use can be cut, but few buildings can say how much, because the tower's supply line is rarely metered on its own.

The office tower is one of the exceptions. Its three chillers (500 RT each) and three roof cooling towers have a make-up sub-meter.

Cooling towers in brief

This course is about water, so we only need a little cooling theory. Cobler's Cooling Fundamentals course explains it fully, starting from how a chilled-water system works.

  • A chiller makes cold water, which we call chilled water, and pumps send it around the building to cool the air. So the chiller takes heat out of the building.
  • The chiller has to dump that heat somewhere, plus the heat from the electricity its compressor uses. In a water-cooled chiller, the heat warms a second water loop, the condenser water, which is pumped up to the cooling tower.
  • The cooling tower sprays the warm condenser water over a packing called fill, while fans blow air through it. A small part of the water evaporates, and that cools the rest. The cooled water returns to the chiller to collect more heat.

We often measure cooling capacity in refrigeration tons (RT), and one RT equals 3.517 kW of cooling (what is a ton of refrigeration). For the fill, fans, drift eliminators and the condenser water loop in more detail, read how a cooling tower works.

Evaporation

So why does a tower use so much water? Because it rejects heat by evaporating part of the water flowing through it. Evaporating a litre of water carries away a large amount of heat. That's why towers work so well, and it's also what sets how much water they use.

Here's the number to remember. A tower evaporates about 1.8 to 2 litres of water per hour for every kW of cooling the chillers deliver.

That's about 6.6 litres for every RT-hour, where one RT-hour is one RT of cooling delivered for one hour. Or call it 1 m³ per hour for every 500 kW of chiller load.

So the office tower at its peak of 900 RT evaporates about 5.9 m³ an hour, before anyone flushes a single toilet. The optional note at the end shows where the 6.6 litres comes from.

Worth knowing: this assumes all the heat leaves the tower by evaporation. In practice, a small part warms the air directly, so real evaporation is a little lower. So treat these figures as a sound upper estimate.

And none of this water use is a fault, because it comes from the physics of how a tower works. No amount of maintenance removes it.

In Malaysia it also goes on all year, because there's no winter shutdown. The plant runs every working day in warm, humid air, with sunlight that feeds algae and bacteria. That's why water treatment matters as much as the water bill.

Cooling tower water consumption, route by route

So the tower loses water, and we have to keep replacing it. The water we buy for the tower is called make-up water, because it makes up for what the tower loses. And it leaves by four routes:

  • Evaporation is the useful loss. It rises and falls with the cooling load. We can't reduce it without reducing the cooling, or making the chiller and the building need less cooling.
  • Blowdown, also called bleed, is water we drain from the tower on purpose to keep dissolved minerals under control. This is the stream we can manage, and the next section explains it.
  • Drift is fine droplets carried out of the tower by the fans. Drift eliminators in good condition hold it to a few thousandths of a percent of the circulating flow. Damaged, missing or badly seated eliminators can lose many times more. The signs are a visible mist plume and a mineral film on cars parked downwind.
  • Leaks and overflow come from float valves that stick open and cracked basins. They also come from a basin overfilling down its overflow pipe, or a make-up valve that never quite closes. These run day and night, and they're often what a water bill investigation finds.
Diagram of a cooling tower with make-up water entering and four outflows labelled evaporation, blowdown, drift and leaks or overflow, with the equation make-up equals evaporation plus blowdown plus drift plus leaks, and a note that only blowdown is controlled by cycles of concentration

Make-up water replaces evaporation, blowdown, drift and leaks. Evaporation follows the cooling load, and drift and leaks should be close to zero, so blowdown is the part we manage.

So the cooling load sets evaporation, and drift and leaks should be close to zero. That leaves blowdown as the real control over cooling tower water consumption. And blowdown depends on something called cycles of concentration.

Try it

Loading the interactive

Cycles of concentration

Picture a pot of tap water simmering on a stove. Steam leaves and the water level drops, but every mineral that came in with the tap water stays behind.

So the water left in the pot gets more and more concentrated. A cooling tower is that pot, running all the time and being topped up as it goes.

How many times more concentrated the tower water is than the make-up water is what we call the cycles of concentration. Three cycles means the water circulating in the tower carries three times the dissolved minerals of the supply from Air Selangor or your state operator.

We usually measure it with a conductivity probe, by dividing the conductivity of the tower water by the conductivity of the make-up water.

To stop the minerals building up forever, some tower water is drained off as blowdown and replaced with fresh make-up. The more cycles the tower runs at, the less it needs to drain. Leaving out drift and leaks, the relationship is:

  • Blowdown = evaporation ÷ (cycles − 1)
  • Make-up = evaporation + blowdown

So at two cycles, blowdown equals evaporation, and total make-up is twice the evaporation. We buy two litres for every one that does useful cooling.

At four cycles, blowdown falls to a third of evaporation, and make-up is about 1.33 times evaporation. So moving a tower from two cycles to four cuts its total water use by about a third, for exactly the same cooling.

At six cycles, make-up is 1.2 times evaporation, but the savings shrink after four or five cycles.

Using the 6.6 litres of evaporation per RT-hour from earlier:

Cycles of concentration

Make-up ÷ evaporation

Make-up per RT-hour of cooling

2

2.0

about 13 L

3

1.5

about 10 L

4

1.33

about 8.8 L

5

1.25

about 8.3 L

6

1.2

about 7.9 L

Now let's try it on the office tower. Its make-up meter reads about 1,350 m³ in a typical month, the same September 2026 month that Part 7 billed.

The water treatment contractor holds about four cycles, and at four cycles, make-up is 1.33 times evaporation. So:

  • Evaporation ≈ 1,350 ÷ 1.33 ≈ 1,010 m³ a month.
  • Blowdown ≈ 1,010 ÷ (4 − 1) ≈ 340 m³ a month.

Say the treatment programme and the water chemistry allowed six cycles. Then make-up would fall to about 1,010 × 1.2 ≈ 1,215 m³, saving about 135 m³ a month. At the RM4.28 cost of one more cubic metre from Part 7, that's about RM578 a month.

It works the other way too. If a stuck bleed valve dropped the tower to two cycles, make-up would rise to about 2,025 m³, costing about RM2,900 a month more.

The limit on cycles

So why not keep pushing the cycles up? Because everything in the water concentrates, including calcium, alkalinity, silica and chlorides.

Once they pass what the make-up water chemistry and the treatment programme can keep dissolved, the trouble starts. We get scale on the condenser tubes and corrosion in the pipework. And we get warm, nutrient-rich water that encourages biofilm and Legionella.

Treated supply in much of Peninsular Malaysia comes from rivers and reservoirs, and it tends to be fairly soft. That usually allows higher cycles than in hard-water regions. But the right limit depends on an analysis of your own make-up water, and on your treatment chemicals.

So ask your water treatment contractor two questions. How many cycles is the programme designed for, and how many is the tower really holding? In many buildings the two numbers are far apart.

The usual causes are ordinary ones:

  • A manual bleed valve opened years ago and never adjusted, draining water at a fixed rate whatever the load.
  • A conductivity controller whose probe is fouled and reads low, so it bleeds all the time.
  • A controller left in manual override since someone was troubleshooting in 2019.

And none of these raises an alarm on its own.

Scale and chiller power

But too many cycles costs more than water. Scale on condenser tubes acts like insulation. So the refrigerant in the condenser has to run hotter to push the same heat into the condenser water.

The gap between those two temperatures is called the condenser approach, and scale widens it. A higher condensing temperature makes the compressor work harder. A common rule of thumb is that each extra 1 °C of condensing temperature costs around 2 to 3 percent of chiller efficiency.

So a tower that's scaling costs us twice, whether the cycles were pushed too high or the treatment programme lapsed. We pay once in make-up water. And we pay again, usually by much more, in chiller electricity every hour the plant runs.

On most Malaysian commercial tariffs, the electricity penalty is far larger than the water saving that caused it. On a chiller plant, water and energy are one problem.

Tower water is also a health risk. A tower sprays warm water into moving air. If the water isn't treated and the tower isn't cleaned, its fine droplets can carry Legionella bacteria.

Managing that risk is part of running a tower, usually with help from a water treatment contractor. Legionella in cooling towers explains the risk and how it's managed. Part 5 of this course covers the separate question of keeping drinking water safe.

Metering make-up

So how do we keep an eye on all this? Not from a monthly bill that lumps the tower in with every toilet in the building.

Start with a dedicated meter on the tower make-up line, with a pulse or Modbus output (Part 6 explains both). Log it every fifteen minutes, instead of reading it by hand once a month.

Where the piping allows, meter the blowdown line as well. Then make-up divided by blowdown gives the cycles of concentration all the time, as long as drift and leaks are small. And nobody has to climb to the roof with a conductivity pen.

Once the data is logging, three checks do most of the work:

  • Litres per RT-hour of cooling. Compare the make-up volume with the chiller load recorded by the building management system (BMS). From the cycles table, a tower holding three to five cycles should use about 8 to 10 litres per RT-hour. That ratio should be stable. If it creeps up, the bleed has opened or something is leaking.
  • The overnight flat line. In an office where the chillers shut down at night, make-up flow should fall to near zero once the basin has refilled. Steady flow at 3am points to a stuck float valve, a leaking basin or an open bleed, running every night. Part 10 covers night flow in detail.
  • Step changes. Use that jumps on a particular date and never comes back down is a valve position or a controller setting. Weather doesn't change like that.

This works best when the tower is one metered branch inside a full building water balance audit, and not a separate project.

There's one more thing worth checking. Water that evaporates from a tower never reaches the drain. Yet the IWK commercial excess charge from Part 7 is based on the water supplied to the premises.

IWK's published commercial schedule doesn't mention an allowance for evaporation. So if your tower make-up is metered separately, ask IWK directly whether any adjustment applies to your account, and don't assume either way.

Optional detail: where 6.6 litres per RT-hour comes from. Evaporating one kilogram (about one litre) of water absorbs about 2,400 kJ. A chiller rejects about 1.25 times its cooling load, because the compressor's energy adds to the heat taken from the building.

So for each kW of cooling, the tower rejects about 1.25 kW, which over an hour is 1.25 × 3,600 = 4,500 kJ. Evaporating that takes about 4,500 ÷ 2,400 ≈ 1.9 kg of water.

One RT is 3.517 kW, so per RT-hour that's 3.517 × 1.9 ≈ 6.6 litres. The table's make-up figures are 6.6 litres multiplied by the ratio in the middle column.

The rest of the bill

So now we know the biggest single user in a building with a cooling tower. We know how to estimate its share, and which part of it we can control. In our tower, that's about 1,350 m³ of the month's water, mostly evaporation and blowdown.

But the bill still says about 3,000 m³. So where did the rest of the month's cubic metres go, and how much of them can nobody explain? That's Part 9: How to Run a Water Balance Audit on Your Building.

Check your understanding

1. A tower's make-up meter reads 900 m³ in a month, and the treatment contractor reports three cycles. About how much was evaporation and how much was blowdown?

Show the answer

At three cycles, make-up is 1.5 times evaporation. So evaporation ≈ 900 ÷ 1.5 = 600 m³, and blowdown = 600 ÷ (3 − 1) = 300 m³. Together they make the 900 m³, assuming drift and leaks are small.

2. In the office tower, the chillers are off overnight. But the tower make-up meter shows a steady 0.5 m³ an hour at 3am every night. What does this suggest?

Show the answer

With no cooling load there should be almost no evaporation, so the flow is probably a loss. It could be a float valve stuck open, a basin leaking or overflowing, or a bleed valve left open.

At 0.5 m³ an hour for ten night hours on 30 nights, that's about 150 m³ a month. At RM4.28 a cubic metre, that's about RM640.

Recap

  • A cooling tower cools condenser water by evaporating part of it. That's about 1.8 to 2 litres per hour per kW of cooling, or about 6.6 litres per RT-hour.
  • Make-up water replaces evaporation, blowdown, drift and leaks.
  • Evaporation follows the load. Blowdown depends on cycles of concentration, where blowdown = evaporation ÷ (cycles − 1).
  • Raising cycles saves water, but water chemistry and treatment set a limit, and scale costs chiller electricity as well as water.
  • Meter the make-up, and ideally the blowdown. Watch litres per RT-hour, night flow and step changes.

This is Part 8 of 12 in Cobler's Water Fundamentals course. Previous: Commercial Water Tariff Malaysia: How Billing Works. Next: How to Run a Water Balance Audit on Your Building.

Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.

FAQ

Frequently asked questions

Ask us about this topic

Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.

0/500

Keep reading