Blog
BMS Sensors and Actuators: A Building's Senses and Muscles
How BMS sensors and actuators work: the temperature, humidity, CO2 and flow sensors that see, and the valves, dampers and drives that move air and water.

Part 2 of 16 in Cobler's Building Automation and BMS Fundamentals course. New here? See the course page.
Think back to level 12 at 7:10 in the morning. The building management system (BMS) somehow knew how warm the floor had got overnight, and then it pushed a chilled water valve open.
But the controller doing all this is a small computer. It can't feel how warm the air is, and it has no hands to turn a valve.
So it relies on two families of hardware fixed to the equipment. Sensors do the sensing, and actuators do the acting.
Let's look at BMS sensors and actuators in turn, on AHU-12A. That's the air handling unit (AHU) that cools the east half of level 12.
From warm air to a number
A controller only understands electrical signals, so something has to translate the world into that form. That's the sensor's job. A sensor is a device that turns a physical condition, such as a temperature or a pressure, into an electrical signal.
Take the return air temperature sensor on AHU-12A from Part 1. It sits in the duct that brings air back from the level 12 offices.
As the air warms or cools, the sensor's electrical signal changes. The controller then turns that signal back into a number, such as 25 °C.
Why does the controller need that number? Because it has to compare it with a target, the setpoint from Part 1.
If the room air reads 26 °C and the setpoint is 24 °C, the controller knows the room isn't cool enough. Without the sensor, the setpoint is only a wish, so every sensor in a BMS is there to give the controller something to compare.
What a BMS measures
So which conditions does a BMS need to compare? Here are the sensors a typical BMS relies on:
- Temperature. This is the most common sensor in any building. It measures the air in a room, the air in a duct, or the water in a pipe. A typical cooling setpoint in a Malaysian office is about 24 °C.
- Relative humidity. In Malaysia, humidity matters as much as temperature for comfort. A humidity sensor reports how much moisture the air holds, as a percentage of the most it could hold at that temperature (relative humidity, RH).
- Pressure. Air ducts and water pipes both have pressure sensors. A duct pressure sensor tells the BMS how hard the fan is pushing the air, so the fan runs only as fast as needed. A water pressure sensor does the same for the chilled water pumps.
- Filter differential pressure. This is the pressure difference across a filter. As the filter collects dust, the air finds it harder to pass through, so the difference rises.
- Carbon dioxide (CO2). People breathe out CO2, so the CO2 level in a room shows about how many people are in it.
- Water flow. A flow sensor, or flow meter, measures how much water moves through a pipe, usually in litres per second. Flow together with temperature tells us how much cooling is being delivered, so it's one of the most useful measurements in the building.
- Electrical power and energy. A power meter measures the kilowatts (kW) a machine draws right now, and the kilowatt-hours (kWh) it has used over time. This is how a BMS knows what its decisions cost.
For humidity, the reference is Malaysia's Industry Code of Practice on Indoor Air Quality 2010 (ICOP IAQ 2010). It comes from the Department of Occupational Safety and Health. It gives 40 to 70% RH as the acceptable indoor range, alongside 23 to 26 °C.
Many designers aim for 50 to 60% within that range. At the humid end, a room feels clammy even when the thermometer says it's cool.
The CO2 sensor lets a BMS bring in as much fresh outdoor air as the people need, and no more. With too little fresh air, the room feels stuffy. With too much, the building spends energy cooling and drying hot, humid outdoor air for no reason.
Worth knowing: for the power meter, the Electricity course explains the difference between kW and kWh in Power vs Energy: kW and kWh Explained.
So what does AHU-12A itself measure? It has four of these measurements:
- the return air temperature
- the supply air temperature, which is the air leaving the AHU towards the offices
- the filter differential pressure
- the fan status, which confirms whether the supply fan is actually running.
Part 6 explains which device should give that fan status signal.

AHU-12A's sensors (blue) measure the air and the filter. Its actuators (amber) move the chilled water valve and set the fan speed.
When a sensor drifts
Now, a reading is only useful if it's accurate, and sensors don't stay accurate forever. Their readings slowly drift over time.
So we check each sensor against a known reference and correct it, and we repeat that at intervals. That's what we call calibration.
The tricky part is that a drifted sensor usually shows a number that looks reasonable, so nobody notices. Let's see what that does in the chiller plant.
The plant judges how much cooling it delivers from two temperatures. One is the chilled water going out to the building, the supply, and the other is the water coming back, the return.
The difference between them is called delta-T, and Part 12 shows how the plant uses it. In the office tower, the design supply is 6 °C and the return is 12 °C, so the delta-T is 6 °C.
Now suppose the return water sensor has drifted and reads 1 °C lower than the truth, so 11 °C instead of 12 °C. The plant now calculates a delta-T of 5 °C instead of 6 °C.
Its estimate of the cooling delivered is about one-sixth too low, so it may run pumps and chillers harder or softer than it should. That wastes energy or leaves parts of the building short of cooling.
And every decision that uses the drifted reading goes wrong in the same direction. That's why sensors are calibrated at intervals, not only when they're installed.
Valves, dampers and drives
So sensors let the BMS measure the building, and actuators let it act. An actuator turns a controller's command into physical movement.
The controller says "open a bit more", and the actuator pushes something open. Most actuators in a building do one of three jobs:
- turn a water tap
- turn an air tap
- change a speed.
The water tap is a control valve. A control valve sets how much water flows through a pipe. On AHU-12A, one on the chilled water pipe sets how much chilled water flows through the cooling coil.
That decides how much heat the coil takes out of the air passing over it. Open the valve further and more chilled water flows, so the air leaving the coil gets colder.
And it can do more than open and shut. A modulating control valve can sit at any position between closed and fully open. So the controller can ask for exactly 37% of full flow, if that's what the offices need.
The part that moves it is the valve actuator, a small motorised device clamped to the top of the valve. It's usually powered at 24 V AC and takes a small control signal from the controller. Its one job is to move the valve to the position it was told and hold it there.
The air tap is a damper. A damper sets how much air flows along a duct. It's a set of blades inside the duct that pivot open and closed, like a Venetian blind.
Dampers decide how much fresh outdoor air comes in, how much stale air goes out, and how air is shared between areas. Like a valve, a modulating damper can sit at any position. It's moved by a damper actuator, which is also a small, low-voltage device.
The speed dial is a variable speed drive. A fan or pump is turned by an electric motor, and the simplest way to run a motor is on or off.
A variable speed drive (VSD), also called a variable frequency drive (VFD) or an inverter, sits between the electricity supply and the motor. It lets the controller run the motor at any speed from slow to full.
That matters for energy. A fan running at half speed uses far less than half the power. So easing a fan off saves much more than you'd guess from its speed.
AHU-12A's supply fan has a VSD, so the BMS can set its speed. Part 13 explains where those savings come from and what limits them.
Worth knowing: to see how a drive works inside, the Electricity course explains it in Power Electronics: Rectifiers and Inverters Explained.
The actuator and the motor
This next point is easy to get wrong, and it comes up all through the course, so let's set it out once here.
A valve or damper actuator is a small, low-voltage positioning device. It takes the controller's command and moves a valve or a damper to the right position, and that's all it does.
The pump, fan or compressor is a different machine. In a commercial building it's usually a three-phase motor on the 400 V supply, doing the heavy work of moving air and water around. AHU-12A's supply fan motor, for example, draws about 6 kW.
So the BMS doesn't power that motor. It sends a command to the motor's variable speed drive, or to a starter, the switch that turns a fixed-speed motor on and off. The drive or starter takes its power from the building's switchboard and runs the motor.

The controller sends small signals. The power that turns the fan motor comes from the switchboard, through the drive.
So we keep two things apart:
- The valve or damper actuator is a small 24 V device that positions a tap.
- The pump, fan or compressor motor is a three-phase 400 V load that does the heavy work, run through a drive or starter.
Mixing them up leads to wrong drawings and wrong decisions, such as expecting a BMS output to power a motor directly.
Worth knowing: a three-phase motor is a 400 V load, measured between the supply lines. The 230 V in a "400/230 V" rating is between one line and neutral, which single-phase lights and sockets use but the motor doesn't. Very large centrifugal chillers may be fed at medium voltage instead of 400 V.
If three-phase supply is new to you, see Three-Phase Power Explained, and the motors themselves are in How Electric Motors Work. You don't need either for the rest of this course.
Analogue and digital
Now look back at every signal we've met. Each one is one of two kinds:
- An analogue signal is a value that can vary smoothly across a range. A temperature of 18.4 °C, a humidity of 55% and a valve at 63% open are all analogue values. Most sensor readings and most modulating commands are analogue.
- A digital signal, also called binary, has only two states: on or off, running or stopped, alarm or no alarm. A fan is either commanded to run or not, and a pump either reports that it's running or it doesn't.
AHU-12A uses both at once. Its controller:
- reads analogue air temperatures and an analogue filter differential pressure
- sends an analogue position command to the chilled water valve
- sends an analogue speed command to the fan's drive
- sends a digital run command to the fan
- reads a digital signal confirming the fan is actually running.
The difference matters because it decides how each device is wired to the controller, and how it's counted. In Part 3 we'll see that a controller's size is described by how many of each kind of signal it can handle.
Follow one analogue reading: a CO2 sensor in a level 9 meeting room of the same tower
Try it
The controller in the middle
So now AHU-12A has its senses and its muscles. Sensors turn the air and water into signals, and actuators turn commands into movement.
But something still has to sit between them and make the decisions. What is that box in the middle, and how does each sensor and actuator connect to it? We'll open it up in Part 3: Controllers, DDC and I/O Points.
Check your understanding
1. AHU-12A's chilled water valve actuator and its supply fan motor both "move" something. Why do we treat them so differently?
Show the answer
The valve actuator is a small 24 V device that positions the valve on the controller's command. The fan motor is a three-phase 400 V machine, about 6 kW here, that does the heavy work of moving air.
The BMS sends the motor's drive a command, and the power comes from the switchboard through the drive, not from the BMS.
2. A chilled water return sensor reads 1 °C low. Why does this matter when the number on the screen looks normal?
Show the answer
The plant judges the cooling it delivers from the supply-to-return difference, the delta-T. With a 6 °C design delta-T, a 1 °C error makes the calculated delta-T 5 °C, so the cooling estimate is about one-sixth too low.
The plant may then run pumps and chillers wrongly, which wastes energy or leaves the building short of cooling.
Recap
- Sensors turn physical conditions into signals the controller can compare with setpoints: temperature, humidity, pressure, CO2, water flow and electrical power.
- Sensors drift and need calibration, and one wrong sensor can mislead every decision that uses it.
- Actuators turn commands into movement. Modulating valves control water, dampers control air, and variable speed drives set fan and pump speeds.
- A valve or damper actuator is a small 24 V device. The pump, fan or compressor motor is a separate three-phase 400 V machine, run through a drive or starter.
- Signals are either analogue (a varying value) or digital (on or off).
Go deeper on video (optional)
This video shows the sensors, valves and dampers on a real air handling unit, the same kinds of devices we placed on AHU-12A. It's optional, and you don't need it for the next part.
This is Part 2 of 16 in Cobler's Building Automation and BMS Fundamentals course. Previous: What Is a Building Management System (BMS)? A Plain-Language Start. Next: Controllers, DDC and I/O Points: The Brain Behind the BMS.
Cobler builds CobiNeural, a platform that shows a facility team its building's energy, water and indoor air data as live numbers across the whole site. To see how your building performs, talk to us.
FAQ
Frequently asked questions
A sensor turns a physical condition, such as an air temperature of 26 °C, into an electrical signal the controller can read. An actuator does the reverse: it turns the controller's command into physical movement, such as opening a chilled water valve or a damper. Sensors let the BMS measure the building, and actuators let it act on the building.
No. A valve or damper actuator is a small low-voltage device, usually powered at 24 V AC. It moves a valve or damper to the position the controller commands. The pump, fan or compressor is a separate machine, usually a three-phase motor on the 400 V supply. The BMS does not power that motor: it sends a command to the motor's variable-speed drive or starter, which takes its power from the switchboard.
An analogue signal is a value that can vary smoothly across a range. Examples are a temperature of 18.4 °C and a valve at 63% open. A digital (binary) signal has only two states, such as on or off, or running or stopped. A single air handling unit uses both: analogue temperatures and valve positions, and a digital run command and running status for its fan.
Ask us about this topic
Something in this article you want to dig into — or a situation in your own building it doesn't quite cover? Send us your question. We don't run public comments; the team replies to you directly by email.


